Ask Experts Questions for FREE Help !
Ask
    c32bvtec's Avatar
    c32bvtec Posts: 4, Reputation: 1
    New Member
     
    #1

    Oct 23, 2007, 07:31 AM
    High water pressure (well water system)
    We are using well ater system and pump and tank set up.. however we have been experiencing the high water pressure lately.. I was told it is the pressure regulator/vavle problem. How do I adjus the pressure.. it is electirc and I think there are two nuts inside the box.. one is bigger than the other.. I think it should be set to 50 psi.. how do I adjust and know which level is 50 psi. high water pressure

    --------------------------------------------------------------------------------

    Hi sir
    Thanks for replying my messagne and I found out that I have square D water pressure regulartor/valve.. so you are saying I need to adjust the small spring nut to reduce pressure.. cause the pressure is at 80 or 90 psi...
    Please advise.thanks a lot
    Thanks
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #2

    Oct 23, 2007, 10:58 AM
    we have been experiencing the high water pressure lately.. I was told it is the pressure regulator/vavle problem. How do I adjust the pressure
    u are saying I need to adjust the small spring nut to reduce pressure.. cause the pressure is at 80 or 90 psi...
    That's what I'm saying.
    80 or 90 P)SI is way too high for house pressure. The average is 45PSI. Click on the image (Square "D" Cutaway) to see the nuts locations.

    First turnoff the power at the breaker box, then pull the cover off the pressure switch and you will see two spring loaded bolts secured with nylon nuts.(see image) One tall, one short. To increase the cut in pressure, turn the nut on the tall bolt down, to decease the cut in pressure back the nut off.. To increase the cut out pressure,(that's the one that will give you more or less pressure) turn the nut on the short bolt down, to decrease the cut out pressure back the nut off. You will have to check your pressure gage as you do this. Good luck, Tom
    c32bvtec's Avatar
    c32bvtec Posts: 4, Reputation: 1
    New Member
     
    #3

    Oct 23, 2007, 02:20 PM
    Quote Originally Posted by c32bvtec
    we are using well ater sytem and pump and tank set up..however we have been experiencing the high water pressure lately..i was told it is the pressure regulator/vavle problem. how do i adjus tthe pressure..it is electirc and i think there are two nuts inside the box..one is bigger than the other..i think it should be set to 50 psi..how do i adjust and know which level is 50 psi. high water pressure

    --------------------------------------------------------------------------------

    hi sir
    thanks for replying my messagne and i found out that i have square D water pressure regulartor/valve..so u are saying i need to adjust the small spring nut to reduce pressure..cause the pressure is at 80 or 90 psi...
    please advise.thanks alot
    thanks
    All right.. I will work on it tonight and thanks for the info
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #4

    Oct 25, 2007, 05:15 AM
    e: about high water pressure
    I appreciate that so much sir
    The name of the well water tank is pro source and it is the air valve on top of it.. I check all the pro source water tanks.and the air valve is all the same on every models.. and it is leaking maybe because I tried to pump some air into the tank yesterday because it is at 0 psi.. and because the air valve is old.. I might have damage the air valve.. and about the pressure switch.. it is made by square d and one big nut and small.and the cut in will be at 30 psi at normal and it will start to pump at 50 psi... is it normal?thanks
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #5

    Oct 25, 2007, 05:36 AM
    The bladder tank pressure should be set at 2 PSI under the cut in pressure on the control box when the pump's shut down anr the pressure's bled off. When yo crack the air valve on the tank does water come out?
    the cut in will be at 30 psi at normal and it will start to pump at 50 psi... is it normal?
    Not the way you explain it. The cut in pressure will be 30 PSI and that will be when the pump starts to work. The cut out point will be 50 PSI and that's when the pump stops.
    Regards, Tom
    c32bvtec's Avatar
    c32bvtec Posts: 4, Reputation: 1
    New Member
     
    #6

    Oct 25, 2007, 05:56 AM
    Quote Originally Posted by speedball1
    The bladder tank pressure should be set at 2 PSI under the cut in pressure on the control box when the pump's shut down anr the pressure's bled off. When yo crack the air valve on the tank does water come out?

    Not the way you explain it. The cut in pressure will be 30 PSI and that will be when the pump starts to work. The cut out point will be 50 PSI and that's when the pump stops.
    Regards, Tom
    Yes water came out
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #7

    Oct 25, 2007, 06:12 AM
    yes water came out( of the top of the bladder tank)
    Then the membrane has ruptured and you will have to replace the bladder tank. Good luck, Tom
    c32bvtec's Avatar
    c32bvtec Posts: 4, Reputation: 1
    New Member
     
    #8

    Oct 25, 2007, 06:21 AM
    Quote Originally Posted by speedball1
    Then the membrane has ruptured and you will have to replace the bladder tank. good luck, Tom
    Besides the water leak.what else can be damaged if I don't replace the bladder tank?
    Thanks
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #9

    Oct 25, 2007, 07:23 AM
    Quote Originally Posted by c32bvtec
    besides the water leak.what else can be damaged if i dont replace the bladder tank?
    thanks
    The tank you have now is useless and every time you draw a glass of water the pump will run. This will overwork the pump and burn out the windings in time. CHANGE THE BLADDER TANK BEFORE ANYTHING ELSE Regards, Tom

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Water pressure too high [ 1 Answers ]

We live in a house where share a well with 3 other houses.what would cause the water pressure to keep going up over 100 psi on my gages . I replaced the pressure tank,the cut off switch 30/50 and all the pipes coming in from the well.where do I look next to solve this problem?

Low water pressure oil hot water heating system [ 1 Answers ]

How does one go about increasing water pressure in a baseboard heating system?

Filling the radiators + high pressure in hot water system... => ? [ 6 Answers ]

Okay, new house to my wife and I... we've had it less than a month and two days ago it was time to turn the heat on. This is an old hot water system, no pump (works by gravity) in a three story house. The radiator in the master bathroom wasn't full, so I tried to bleed it. Just a little air...

How do I increase H2O pressure on well system with a water filtration system? [ 2 Answers ]

Howdy, I would like to know how I can increase my water pressure. My current system uses a well pump with a small pressure tank, and "D" control valve. It then runs through a WATERSOFT filtration tank, RAINSOFT water softner, and on the Hot water side, an AQUASTAR on demand hot water system. I...

Low water pressure in an area known for high pressure [ 3 Answers ]

Greetings, My wife and I are in the process of updating 1957 side by side split level. The previous owner (OK, my Mom as I bought the house I grew up in from her) said that when they moved in they had to install a pressure reducer into the line. I have searched high and low but, I can't see...


View more questions Search