New Member
|
|
Feb 6, 2008, 08:29 AM
|
|
Do non-loop hot water recirculators work?
I am doing a kitchen remodel and would like to add a hot water recirculator. My plumbing runs through the slab so the kind with a dedicated return line to the hot water heater is not feasible.
I've heard that they have systems that use a pump to bleed the hot water into the cold water line. However, my contractor said he installed one of these and it did not perform as advertised. If that's true I'm wondering how much better it is than nothing.
Has anyone had experience with these kinds of systems? It currently takes a couple of minutes to get hot water at my kitchen tap which is not only annoying but wastes water in a desert area.
TIA...
Steve
|
|
 |
Ultra Member
|
|
Feb 6, 2008, 08:49 AM
|
|
Steve -
I've used the Laing Thermotech Autocirc pump for more than 5 years, and I think it is the greatest. Mine is installed in the upstairs master bathroom, which used to take several minutes to get hot water (from the water heater in the basement). Now, I get hot water in seconds. Back then it cost around $250. It is worth it!
The Autocirc is quiet when running, which was a concern of mine. One thing I did have to add later is a water hammer arrester, since I got a thump whenever the pump shut off (when it reached the hot temperature). I used the Sioux Chief unit on both the input and output sides of the pump.
Best of luck,
Wally H.
|
|
 |
Home Repair & Remodeling Expert
|
|
Feb 6, 2008, 08:56 AM
|
|
I am not that familiar with the recirculator but it appears its using power when the water temp drops 24/7. You may want to look into a point of use tankless heater. Rheem, Rinnai and many others all make them. Until 1-1-08 you could get a $300 energy credit on your tax bill but I'm not sure if this will be renewed for 2008. Tankless Water Heater Buying Guide
|
|
 |
Ultra Member
|
|
Feb 6, 2008, 10:29 AM
|
|
 Originally Posted by ballengerb1
I am not that familiar with the recirculator but it appears its using power when the water temp drops 24/7. You may want to look into a point of use tankless heater. Rheem, Rinnai and many others all make them. Until 1-1-08 you could get a $300 energy credit on your tax bill but I'm not sure if this will be renewed for 2008. Tankless Water Heater Buying Guide
There is a timer that allows you to specify a range of times when the pump is to work, however, it uses such an insignificant amount of electricity that I leave it running all the time. The pump only runs when the water temp drops below a certain threshold anyway.
FYI,
Wally H.
|
|
 |
Home Repair & Remodeling Expert
|
|
Feb 6, 2008, 03:31 PM
|
|
A bit pricey but sounds like it does the trick. Since these units do not use a piped looped I am still uncertain how they work. Anybody got a laymans explanation?
|
|
 |
Ultra Member
|
|
Feb 6, 2008, 04:00 PM
|
|
Having installed a number of them without any issues, I'm with Wally on the Laing pump.
|
|
 |
Uber Member
|
|
Feb 6, 2008, 06:48 PM
|
|
How they work: I can guess.
Suppose you put a check valve (one way hot to cold side) with say a 10 PSI differential. Meaning it will take 10 PSI to open it at the furthest fixture.
If there is no pump or the pump is off, there is no difference compared to regular plumbed.
If you add a pump on the hot pumping toward the cold (check valve) with a bypass, then again the hot water flows normally if the pump is off. Water just flows around the pump.
If you turn on the pump, warm water moves to the cold side until it turns hot.
The trick is in the controls.
If you you it all the time, you'll end up with hot water in the cold and hot sides.
If you run it for just enough time to empty the hot water line of warm water, you have made the cold water slightly warm and the warm water standing in the pipes hot. If you turn off the pump, you can draw water from the cold tap which was slightly warm and it will eventually become cold.
So the trick is figuring out when to stop the pump and when to run it.
The simplest: Push a button every time you use the tap to empty the hot water line.
Next simplest: Anticipate when you will use water and use a timer to run the pump briefly.
So, make it a little more complicated. Use a timer to run the circulator loop when you anticipate water use and use a temperature sensor to stop/start the pump.
So, it just has to move the water until the cold temperature reaches a preset value and run it until it happens or there is excess run time. Like run until 85 F, but shut off in 10 minutes. Cause a recirculate before you anticipate using water or disable recirculate at times.
Does the explanation help?
|
|
 |
Ultra Member
|
|
Feb 7, 2008, 04:32 AM
|
|
 Originally Posted by KeepItSimpleStupid
How they work: I can guess.
...snip...
So the trick is figuring out when to stop the pump and when to run it.
The simplest: Push a button every time you use the tap to empty the hot water line.
Next simplest: Anticipate when you will use water and use a timer to run the pump briefly.
So, make it a little more complicated. Use a timer to run the circulator loop when you anticipate water use and use a temperature sensor to stop/start the pump.
So, it just has to move the water until the cold temperature reaches a preset value and run it untill it happens or there is excess run time. Like run until 85 F, but shut off in 10 minutes. Cause a recirculate before you anticipate using water or disable recirculate at times.
Does the explanation help?
The Laing Autocirc has a thermostat built in that will automagically start the pump when the water is cold and stop it once enough water has been pumped to bring it up to temperature. No button to push. There IS a timer, but that simply determines when you want the thing to be completely off. I choose to leave it on all the time and just let the thermostat do its thing. You never know when you'll want hot water in the bathroom (where mine is), but in the kitchen, you might be able to specify a timeframe.
HTH,
Wally H.
|
|
 |
New Member
|
|
Dec 14, 2012, 11:09 AM
|
|
Hey Wally,
I'm getting that thump every time the pump shuts off and put a water hammer arrester on one side, but it still happens. I see you recommended putting one on both sides. My question is, when you installed the Sioux Chief water hammer arrestors on both sides of your Laing Thermotech autocirc pump, did you install the arresters directly to the wall valves and then run a hose to the pump? Or did you connect the arresters directly to the pump with hoses then returning to the valves?
I hope I'm not too confusing here. So I'm basically wondering which of these you did:
1. Wall valve -> hose -> water hammer arrester -> Laing autocirc
Or
2. Wall valve -> water hammer arrester -> hose -> Laing autocirc
Thanks,
JMG
|
|
Question Tools |
Search this Question |
|
|
Add your answer here.
Check out some similar questions!
Hot water loop off a steam furnace
[ 1 Answers ]
My 3 year old furnace heats steam radiators in the house. A hot water loop was installed to heat hot water radiators in the extension. No nail holes have been found in the piping yet air always gets into the system, flooding the furnace. Should the hot water part of the house have its own...
Hot Water doesnot work in Bathtub (but does in Shower)
[ 4 Answers ]
The hot water does not work in any of my three bath tubs. It will start hot (130 degrees) but within 3 minutes the temperature is down to 70 degrees. The showers work that are connected to the bathtub, and all taps in the house have constant hot water. What could my issue be?
Cold Water work, Hot water is only a trickle
[ 3 Answers ]
Recently I've had a drop in the volume of hot water that is coming through my system. It is a problem on every faucet in the house. The cold water pressure is GREAT. The house is 7 years old, and I believe that it has copper tubing throughout. I've been digging around for solutions to this for...
Hot water recirculating pumps do work, but
[ 2 Answers ]
I can attest that the installation of a hot water recirculating pump (and sensor valve) does work. Hot water very quickly for the morning shower, really! However,.
The 'however' is that I find that while the pump is on (in the AM for ~1-1.5 hr.), the hot water and cold water mixing in the...