    Causes of cracked cast iron drain
    Can anyone enlighten me on why a vertical cast iron stack would crack? I have one section of pipe that cracked about 4 feet vertically in an interior wall... and I think I have another big crack in another wall.

    I guess the obvious answer is rust... or extremely hot water in a cold pipe?

    I'm replacing the first 4' section tonight, but I'm concerned that, depending on the reason behind the crack, I may find myself replacing the entire stack in that wall.

    Ideas?
    iamgrowler's Avatar
    iamgrowler Posts: 1,421, Reputation: 110
    Ultra Member
     
    #2

    Mar 20, 2007, 09:43 AM
    Quote Originally Posted by deanrinehart
    Can anyone enlighten me on why a vertical cast iron stack would crack? I have one section of pipe that cracked about 4 feet vertically in an interior wall...and I think I have another big crack in another wall.

    I guess the obvious answer is rust...or extremely hot water in a cold pipe?

    I'm replacing the first 4' section tonight, but I'm concerned that, depending on the reason behind the crack, I may find myself replacing the entire stack in that wall.

    Ideas?
    Is it old hub and spigot pipe, or is it newer no-hub pipe?
    deanrinehart's Avatar
    deanrinehart Posts: 5, Reputation: 1
    New Member
     
    #3

    Mar 20, 2007, 09:55 AM
    Pipe was installed around 1927, my relatively new experience tells me it's bald and bell (is that hub and spigot?).

    Also... I'm making the assumption that the only repair for a crack this length... almost the full section of pipe itself... is replacement, correct? At its widest it's about 3/16 inch.

    The pipe is supported by bells above and below, so I'm planning on cutting about 4-6" from each end and putting bands around with PVC in between. The bells on both ends should be all the support the pipe needs.
    iamgrowler's Avatar
    iamgrowler Posts: 1,421, Reputation: 110
    Ultra Member
     
    #4

    Mar 20, 2007, 10:00 AM
    I've never heard of the older, heavier cast iron cracking like that before, especially along the full length.

    I have seen it happen with newer cast iron, though.

    Usually because the chain on the snap cutter was rounded over and crushed the pipe instead of cutting it.
    deanrinehart's Avatar
    deanrinehart Posts: 5, Reputation: 1
    New Member
     
    #5

    Mar 20, 2007, 10:02 AM
    Oh... and I have to assume that, given the possible compromised ends of this pipe, cutting with a pipe cutter is preferred over the relatively violent sawzall method...
    deanrinehart's Avatar
    deanrinehart Posts: 5, Reputation: 1
    New Member
     
    #6

    Mar 20, 2007, 10:09 AM
    I'll grab some pictures tonight and post. My father, who was a plumbers apprentice way back, is also a bit perplexed. Given that we may be seeing this elsewhere in this house, we were thinking bad batch of pipe, but the tool theory works as well.

    Given that we're talking about 2 odd compromises visible in a house with 5 separate stacks running about 28' vertical each... I may be in for a fun summer.
    iamgrowler's Avatar
    iamgrowler Posts: 1,421, Reputation: 110
    Ultra Member
     
    #7

    Mar 20, 2007, 10:16 AM
    Quote Originally Posted by deanrinehart
    I'll grab some pictures tonight and post. My father, who was a plumbers apprentice way back, is also a bit perplexed. Given that we may be seeing this elsewhere in this house, we were thinking bad batch of pipe, but the tool theory works as well.

    Given that we're talking about 2 odd compromises visible in a house with 5 separate stacks running about 28' vertical each...I may be in for a fun summer.
    The pipe manufactured in the twenties was some pretty thick, tough stuff.

    And then it went all to heck during WWII (thinner walled and shallower hubbed), and stayed that way during the housing boom immediately following the war.

    Just as they were starting to cast some decent pipe again, ABS and Copper came along and stole it's thunder.
    iamgrowler's Avatar
    iamgrowler Posts: 1,421, Reputation: 110
    Ultra Member
     
    #8

    Mar 20, 2007, 10:18 AM
    Quote Originally Posted by deanrinehart
    Oh...and I have to assume that, given the possible compromised ends of this pipe, cutting with a pipe cutter is preferred over the relatively violent sawzall method...
    If you rent a chain cutter, try to find one of the smaller cutters manufactured by Reed, they are much lighter and less likely to knock you off a ladder when cutting overhead.
    deanrinehart's Avatar
    deanrinehart Posts: 5, Reputation: 1
    New Member
     
    #9

    Mar 20, 2007, 10:24 AM
    Quote Originally Posted by iamgrowler
    The pipe manufactured in the twenties was some pretty thick, tough stuff.
    There is a chance that this is the thinner pipe. The wall behind the pipe... a flight of stairs and a store room... looks to be a different, newer type of metal lath. This may be a post WWII replacement.

    Great.
    doug238's Avatar
    doug238 Posts: 1,560, Reputation: 62
    Ultra Member
     
    #10

    Mar 20, 2007, 08:20 PM
    I would not use a chain cutter on old cast iron pipe that is breaking down. I use a lenox blade 656r or the 8 inch, on slow speed. Keep the foot of the sawzall hard against the pipe the whole time. It will amaze you how fast and clean this blade cuts old or new cast iron. The chain cutter will crush one side and will no longer be able to cleanly cut it.
    That lenox blade is a wood blade, but trust me on this one.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Leak In Cast Iron Drain [ 1 Answers ]

I live in a house that is over 40 years old. There is a leak in the basement that is coming from the drain in the kitchen above. Water is coming through or under the block wall about 8 feet from the line from the kitchen. This line goes to a septic tank and appears to go through the slab. How do...

Cast iron drain connection [ 4 Answers ]

Hi, we have a house built in the ealy 50's. We've torn out a small tiled shower and want to replace with a new one that doesn't leak. We have a 2" cast iron drain pipe sticking 1 1/2 inches above the house slab. What is the best way to connect a new two piece drain before we build or install new...

Cracked cast iron bell [ 6 Answers ]

cracked cast iron bell -------------------------------------------------------------------------------- I have been remodeling amy bathroom and the toilet flange was some kind of metal going into the cast iron drain pipe. I cut the metal down to the cast iron then took out the metal in the...

Converting cast iron floor drain to shower drain [ 3 Answers ]

I am adding a bathroom to my basement, which has partial (complete? ) plumbing already roughed into the floor (in 1976). Sewage lift station (vented) is 3 ft from 4" styrofoam plug (toilet), 4 ft from 1 1/2 inch cast male pipe end extending through floor (lav, have already added vertical vent...


View more questions Search