    Mr Shove L's Avatar
    Mr Shove L Posts: 11, Reputation: 1
    New Member
     
    #1

    Aug 26, 2008, 11:41 AM
    1 valve shut off hot water tank valve
    I was just trying to get some Pro's thoughts on, why there would be a shut off valve on the hot line going out of my hot water tank, and no valve on the cold coming in? Is there a reason for this? Is it OK to add a valve on the cold,so I can isolate the tank, by shuting both valves , and would the 3/4 " sweat joints hold under pressure if I want to disconnect and change tanks? I see the same set up a lot at other sites. Thanks for any clues you guys have! Even the shut of on the cold would serve me better! It seems.
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #2

    Aug 26, 2008, 11:52 AM
    Hi Mr. Shove L:

    Code requires that a shutoff be installed in the cold water inlet into the water heater so you can do exactly what you suggested... isolate the water heater if needed.

    Sometimes we see them on just cold, sometimes both hot and cold and rarely just on the hot water like yours... lucky guy!

    I would shut off the main water supply to the house, drain water from the faucets, turn water heater thermostat dial to low temp. and then drain the water heater to at least 6 inches below rim of the heater. Then I would have you install a BALL VALVE...can be sweat or compression type. I have much greater confidence in the sweat type of ball valve... but the compression type work fine and are acceptable... ;)

    If you really want to step it up you could install a floodsafe automatic water heater shutoff with sensor (see picture below). This simply cuts into the cold water supply pipe and then gets sweat fit to the pipe. Thereafter, if sensor (placed on floor at low point or inside a water heater pan) senses water it automatically shuts cold water into heater to stop any possible floods... just another thought.

    Let me know what you think or if need info. On soldering!

    MARK
    Attached Images
       
    Mr Shove L's Avatar
    Mr Shove L Posts: 11, Reputation: 1
    New Member
     
    #3

    Aug 26, 2008, 03:42 PM
    Thanks a lot Mark. I like your ball valve suggestion, I got it on the work bench ,ready to install tomorrow. Thanks for the confidence,
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #4

    Aug 26, 2008, 03:51 PM
    Glad to help!

    Good luck... MARK
    afaroo's Avatar
    afaroo Posts: 4,006, Reputation: 251
    Ultra Member
     
    #5

    Aug 26, 2008, 05:23 PM
    Hi Mark what do you think of the sharkbite ball valve or you are against it, Thanks.

    John
    Attached Images
     
    letmetellu's Avatar
    letmetellu Posts: 3,151, Reputation: 317
    Ultra Member
     
    #6

    Aug 26, 2008, 05:37 PM
    Quote Originally Posted by Mr Shove L
    I was just trying to get some Pro's thoughts on, why there would be a shut off valve on the hot line going out of my hot water tank, and no valve on the cold coming in? Is there a reason for this? Is it OK to add a valve on the cold,so I can isolate the tank, by shuting both valves , and would the 3/4 " sweat joints hold under pressure if I want to disconnect and change tanks? I see the same set up alot at other sites. Thanks for any clues you guys have!! Even the shut of on the cold would serve me better! It seems.
    A cut off valve should never be placed on the inlet side where the cold water enters unless you know that you have a working temperature and pressure relief valve. This valve, in the cold water line would block the water line and stop steam from escaping into the cold water line if you should have a problem where the fire does not shut off and steam accumulates in the water heater tank. And yes I know that most water heaters, if not all have an automatic cut off built into the thermostat. But in a lot of the plumbing industry you try to back up all possible causes for injury or death to the users or workers.
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #7

    Aug 26, 2008, 05:56 PM
    Hi John:

    I'm good with the sharkbite fittings threaded into an I.P.S. ball valve like you posted... but not within 18" of the top of the water heater. As a general rule I don't use plastic pipes (pvc or cpvc), pex pipes (viega, wirsbro, zurn) or sharkbite fittings (orings and plastic parts) near the heater as mentioned. If water heater did malfunction or have backdraft condition from gas flue could melt these and cause more issues for owner. If electric, not quite as important, but I generally follow same rules for both gas and electric.

    Letmetellu is correct if the cold water shutoff gets closed then yeah... better be a T&P valve (see pictures) in place... course, if no T&P valve in place and excess temp. or excess pressure builds up here's what can happen.. click on this for a show!!

    Water Heater Blast!

    Click on the low res. video at mid-bottom of the page.

    Code requires that the T&P valve be installed during installation and that the pipe be terminated in a non-threaded fitting (pipe ends plain end about 6-12 inches above floor) so people can't just plug this wondeful little device and endanger their families/homes, etc. Of course, code also requires that a shutoff be installed in cold water inlet so not a bad idea to check that the T&P valve was installed...just in case!!...;)

    Mr. Shove L:... any concerns... let us know.

    MARK
    Attached Images
      
    afaroo's Avatar
    afaroo Posts: 4,006, Reputation: 251
    Ultra Member
     
    #8

    Aug 26, 2008, 07:05 PM
    Mrak very good explanation,Thanks.

    Regards,
    John
    Mr Shove L's Avatar
    Mr Shove L Posts: 11, Reputation: 1
    New Member
     
    #9

    Aug 28, 2008, 09:59 AM
    Thanks for the reminder !That's a big 10/4 on the T&P valve! And a HOLY _hit on the video.! It's a wonder it don't happen more often (explosion) ,when people get water turned off for non payment? Are T&P is on and working fine... Thanks for help! And I have another question on the water heater , but I'll do it on a new title. Thanks again. Shovel
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #10

    Apr 20, 2010, 05:22 AM
    Thanks for the thumbs up Sumiya!

    Mark

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Water shut off valve [ 2 Answers ]

I am replacing a water shut off valve. The compression valve I purchased says to NOT use plumber's putty however all "how to" pages I check say to always use putty or teflon tape. I am comfused as to what to do.

Can one shut off water main valve but leave gas hot water tank on? [ 4 Answers ]

I would like to know if I go away for two days and shut my main water shutoff valve can I leave my gas hot water tank on. I saw two answers To a similar question and one answer said you can leave it on and the other Said you had to shut it off. I am confused now as to whether I can leave the gas...

Leaky water shut-off valve [ 1 Answers ]

I just replaced 18 year old shut off valves under sink with newer style ones. I replaced the old nut and ferrule as well on copper pipe. I am getting a leak between nut and copper pipe. I have tightened nut quite a bit and still keep getting drips.

After shutting off the water from the shut off valve [ 2 Answers ]

I own a 3 flat and after shutting down the water from the shut off valve, upon turning it back on the water pressure has not been the same. There is a lot of noise in the pipes when Turning on the water. And the Water tank girggles some times, when it never did this before. It sounds like...

Water Shut-off Valve [ 1 Answers ]

I am attempting to replace the valve supplying water to the toilet water tank, but am unable to unscrew it. It turns, but it does not come off. What can I do? Need help ASAP! Thank you!


View more questions Search