    grounded delata power system
    hi guys,
    anybody who can explain me the grouded delata power system?
    I have seen one installation in ksa wherein a delta seconondary of a three phase transformer wherein one of the phase leads is connected to ground.
    the voltage reading is as ff.
    phase A to Grnd = 230
    phase B to Grnd = 230
    phase C to Grnd = 0

    phase to phase

    A-B =400
    A-C = 230
    B-C=230
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jan 22, 2007, 07:57 AM
    Grounding one leg of a Delta system is typical and recommended, sometimes called a "corner ground". Grounding one leg will insure that a fuse or circuit breaker will operate in the even of a short.

    Delta ungrounded systems are sometimes desired, but need a ground falut detection system to at least indicate the presence of a ground fault that can be repaired at a scheduled time.
    danar's Avatar
    danar Posts: 69, Reputation: 2
    Junior Member
     
    #3

    Jan 22, 2007, 09:31 PM
    It looks like we are having a ground fault in this scheme. Is there any effect on our ground fault protection.
    In this kind of connection what is the voltage limitation?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Jan 23, 2007, 03:40 AM
    Any voltage can be had depending on the spes of the transformer.

    I do not understand your question:

    it looks like we are having a ground fault in this scheme. is there any effect on our ground fault protection
    danar's Avatar
    danar Posts: 69, Reputation: 2
    Junior Member
     
    #5

    Jan 28, 2007, 02:37 AM
    What I mean is that the ground fault protection in the primary side of the transformer can sense a fault current if one lead in the secondary is grounded.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #6

    Jan 28, 2007, 05:41 AM
    No, both sides will each need a GFI sensing relay.A GFI on the Primary will only detect a fault in the windings of the transformer.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Car won't start, no click and no power to radio, power window or locks [ 6 Answers ]

After installing a new starter on a 1999 2WD Explorer it will not start. There is no click when trying to start it, its just dead, and the radio, power locks/windows, a/c, and dash light don't work but the interior lights work and so do the headlights. We've had the starter checked to make sure...

Install new ground wire for non-grounded receptacles [ 5 Answers ]

I am planning on running grounds to my upstairs plugs that are currently K&T with the two hole groundless plugs. Question is, can I run several of the grounds into a centrally located j-box and then just run one larger ground back to the panel? I can't imagine running a separate wire for...

Problem with grounded neutral. [ 1 Answers ]

I have an exterior GFCI receptacle that failed. I bought a new GFCI to replace this one. When I opened the outlet box, I discovered that the ground was tied both to the ground screw on the receptacle as well as the neutral plate. I thought I would correct this with the new GFCI receptacle, but...

Outlets(receptacles) not grounded... what to do? [ 4 Answers ]

I embarked on a project to replace all the 15amp duplex wall receptacles in my living room yesterday because I wanted white outlets instead of the black ones that were installed. So I turned off the power and started to swap them out. They are 15amp duplex, 125-volt u-grounded receptacles. Much to...

How do I increase H2O pressure on well system with a water filtration system? [ 2 Answers ]

Howdy, I would like to know how I can increase my water pressure. My current system uses a well pump with a small pressure tank, and "D" control valve. It then runs through a WATERSOFT filtration tank, RAINSOFT water softner, and on the Hot water side, an AQUASTAR on demand hot water system. I...


View more questions Search