    Chilled system
    Hello every body, this is the first time I have visited thes site, and I have aquistions:

    1- could any body has or know any details about the cooling tower connection accessories ( GV,DRV,Y-STR,MBV) for the inlet and outlet pipes

    2- actually I have a colsed chilled water system,water coled chiller ,and I have planned to design a manual chemical dosing unit for my system,but I need for that the formula and the design details.

    3- I want to know where I suppose to connect the expantion tank at the highest or lowest point? At the supply or the return line?

    And whate is the suitable accessories for the tank?

    Regards
    Quantum's Avatar
    Quantum Posts: 38, Reputation: 2
    Junior Member
     
    #2

    Mar 17, 2009, 05:41 AM
    1- Inlet line: gate valve, Double requlating valve or commissioning set or constant flow valve, Motorized butterfly.
    Outlet line: basket strainer, gate valve

    2- The supplier will calculate the capacity: normally for closed system, little chemical is required since the water is not exposed to ambient (unless there is a leak in the system, and make up water is added) and normally the supplier provide a 60 liter tank which can serve for more than 1 year.

    3- The expansion tank can be either on the highest level of lowest level. Most of the time on the highest level if possible will result on a smaller tank.

    The accessories are sight glass, tank filling cnnection and drain valve