    York scroll Compressor won't run on generator power
    I upgraded to a York 15 SEER 4 ton 2 stage AC (DNX024-048) I also have a Generac 20kw natural gas generator. My previous 4 ton 10SEER AC (with a much higher LRA) started just fine on generator power. The new unit's compressor won't start on generator power. The fan will run and it will attempt to start but all it does is make our ceiling fans hum and dim the lights slightly. I am being told by YORK it doesn't recognize the generator's sine wave as a correct sine wave and treats that as low power and therefore won't start. I'm being told by Generac that I just need a Line Conditioner. Is there a way to determine what the issue is and then what the solution needs to be?
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #2

    Jul 27, 2009, 05:56 PM

    Someone could do a power quality analysis. Some UPS systems are frequency sensitive, but the compressor has me slightly baffled.

    A couple of thing to look at:

    Turn the AC off. Go on generator power. Wait 5 minutes. Turn on AC. Does the AC start within 10 minutes?

    I'd make sure that guidelines for the install of compressor heaters and hard-start kits are followed.

    I'd add a hard start kit. Here is one for 5 ton. Hard Start Kit,5.0 Ton A/C Units {Dayton 1BAF1}[1BAF1]

    HOME AC | HVAC replacement systems | HVAC repair systems | HVAC parts: a/c motor repair parts condenser

    Check the grounds. Although this should be more of a heating issue.
    letmetellu's Avatar
    letmetellu Posts: 3,151, Reputation: 317
    Ultra Member
     
    #3

    Jul 27, 2009, 07:21 PM

    There is a cheaper way to use a starting kit

    Kickstart®Hard Start Devices - Home Owner FAQ's
    bobrath's Avatar
    bobrath Posts: 3, Reputation: 1
    New Member
     
    #4

    Jul 28, 2009, 01:35 PM
    Thank you for your responses. A hard start kit was my initial direction as I had one on my previous unit just to help if the generator had a heavier load than normal. I was told by an AC professional that a hard start kit would not help a scroll compressor type unit. Your information along with looking at the links you provided tells me that the original simple cure of using a hard start kit is exactly the correct answer. It appears that the torque is the issue and the Kickstart Hard Start Device will solve that problem. Thanks for your responses and your time.
    bobrath's Avatar
    bobrath Posts: 3, Reputation: 1
    New Member
     
    #5

    Jul 28, 2009, 01:40 PM
    Thank you for your responses. A hard start kit was my initial direction as I had one on my previous unit just to help if the generator had a heavier load than normal. I was told by an AC professional that a hard start kit would not help a scroll compressor type unit. Your information along with looking at the links you provided tells me that the original simple cure of using a hard start kit is exactly the correct answer. It appears that the torque is the issue and the Kickstart Hard Start Device will solve that problem. Thanks for your responses and your time.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #6

    Jul 28, 2009, 04:16 PM

    Not all hard start kits are the same. A potentail relay and a cap should only be used.

    See:

    YouTube - Hard Start Test! Not all Hard Start Kits are the same!

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Power from fifth wheel is 30 amp to generator 120/240 [ 2 Answers ]

We a generator honda gx390 6500 120/240 we just bought a fifth wheel that has a power cord which is a 30 amp we would like to run everything in the trailer with out burning something up so any help at all would be super Thanks for your time

50 Amp Generator Power Cord? [ 4 Answers ]

I'm having a Tough time finding a 50', and a 25 foot Power cord for a Generator. Generator Has 50 Amp 4 Prong Twist lock, and the Power inlet has 3 prong twist lock with the center pin(California Style). Any Ideas, Local suppliers cannot find. Also have a tough time finding a Square D QOT 3030...

Running an air compressor off a generator? [ 1 Answers ]

I am trying to run a 220v air compressor using a gas powered generator. The outlet on the generator is a NEMA 18-30 4pole, 4wire. The air compressor has a 3 wire pigtail on it? How can I get this to work??

Power generator? [ 2 Answers ]

How does power generator works ?


View more questions Search