    JBELL558's Avatar
    JBELL558 Posts: 3, Reputation: 1
    New Member
     
    #1

    Dec 19, 2008, 02:06 PM
    York furnace blowing cold air.
    I have an 11 year old York furnace that intermittenly blows cold air :confused:. When I turn the power to the unit off and back on, it lights normally and will run fine for a few days. This seems to be occurring at night and from the temperature of the house must be when our setback thermostat returns to daytime temperature. I've replaced the flame sensor and checked voltages but it is still occurring. Any help would be much appreciated!
    21boat's Avatar
    21boat Posts: 2,441, Reputation: 212
    Ultra Member
     
    #2

    Dec 19, 2008, 04:38 PM

    This is way out from left field Do you have oil,gas or L.P. On a gas line installation I have seen the gas line 'T" fitting without a drip leg and just a 90 elbow to it. In my area its required to have a 6" min. drip leg and cap below the 'T" fitting so condensation/moisture/water doesn't get into the flame. I will keep thinking on this. Did you change the air filter for the air return? Let us know what the fuel is and start from there or if you have a oil burner
    JBELL558's Avatar
    JBELL558 Posts: 3, Reputation: 1
    New Member
     
    #3

    Dec 20, 2008, 09:06 AM
    This is a natural gas furnace. From the research I've done, I'm beginning to lean towards the pressure sensor, the line that feeds the sensor, or the control panel itself. Hoping to run some tests with my ohmmeter today.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #4

    Dec 20, 2008, 09:34 AM

    Consider this: you may have a clogged condensate trap or drain tube. The longer recovery cycle it runs in the AM is resulting in condensate flooding.
    JBELL558's Avatar
    JBELL558 Posts: 3, Reputation: 1
    New Member
     
    #5

    Dec 20, 2008, 11:07 AM

    THANKS! Will check those items this afternoon.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

York furnace flash error code 6 times (blowing cold air) [ 3 Answers ]

Hello, I have a York (forced air) gas furnace that's 9 years old. Every winter it seems like I have to replace the pressure switch ( round switch with 2 connections & air hose). I hear the blower come on, burners ignite and then within a few seconds they go off with the red light flashing 6 times....

Furnace blowing cold air [ 8 Answers ]

I have a Goodman gas furnace that is about 3 years old. We turned it on for the fall a few weeks ago and it was working just fine. Recently one morning I realized that the blower had been on for a couple hours and I was still cold. All the basic things have been checked. The system is set to...

Furnace blowing cold air.starts out warm, goes to cold. [ 6 Answers ]

Hoping for help here. I recently had my ignitor replaced. Before that, the furnace wasn't working at all. Now it starts blowing warm (not hot) air, then gradually over a period of a couple of hours, the air cools down until it is completely cold and the temperature in the house drops drastically....


View more questions Search