    York Diamond 80 With New Control Board
    Hello. I have a York Diamond 80 furnace with a new Emerson S1-33109167000 control board. The problem began when the fan wouldn't turn off even though the A/C compressor had turned off. The original control board had gone bad and was replaced. But, the fan still keeps on running. The led has a steady green flash which the codes list says means that all is normal.I have heard that control boards can be wired so that the fan runs all of the time. Could this be the problem? If so, is there a way to fix this?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Sep 3, 2009, 05:46 AM
    Luxair is a division of York so this sheet will work for you.

    http://www.luxaire.com/PDFFiles/035-...001-B-0208.pdf

    NOTE: Check to be sure your thermostat is set to auto and NOT on for fan operation.

    Also check the thermostat cable for shorts by removing the GREEN thermostat wire from the circuit board. If after removing the green wire the fan shuts off there is a wiring/thermostat problem. If the fan keeps running then issues with the control board will need to be addressed. NOTE when removing the green wire after you turn the power off make sure it is insulated or tape protected so it cannot touch anything and cause a short circuit.
    waldolc's Avatar
    waldolc Posts: 5, Reputation: 1
    New Member
     
    #3

    Sep 3, 2009, 07:26 AM
    Quote Originally Posted by hvac1000 View Post

    NOTE: Check to be sure your thermostat is set to auto and NOT on for fan operation.

    Also check the thermostat cable for shorts by removing the GREEN thermostat wire from the circuit board. If after removing the green wire the fan shuts off there is a wiring/thermostat problem. If the fan keeps running then issues with the control board will need to be addressed.
    Thank you for your help. After disconnecting the GREEN wire from the control board the fan still came on. I know that the old board was bad because I saw where a part had burnt through. I inspected the wiring and it is connected the same way as it was to the old board. When I switch the unit to HEAT the fan turns off as it should. Only when it's on A/C does it run continuously.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    Sep 3, 2009, 07:31 AM
    It is possible the board is defective or the fan selection switch on the circuit board is not adjusted properly. I make a assumption that this is just a standard system with no added relays etc. I will be back later on this afternoon to answer your reply.
    waldolc's Avatar
    waldolc Posts: 5, Reputation: 1
    New Member
     
    #5

    Sep 3, 2009, 07:46 AM
    Quote Originally Posted by hvac1000 View Post
    It is possible the board is defective or the fan selection switch on the circuit board is not adjusted properly. I make a assumption that this is just a standard system with no added relays etc. I will be back later on this afternoon to answer your reply.
    Thank you. Well, the board still flashes the green heartbeat. The fan selection switch?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #6

    Sep 3, 2009, 09:43 AM
    The fan selection switch?

    You can give that a shot but under normal conditions in the A/C mode the fan should shut off when the ouitside unit shuts off or soon there after. OR when the green wire is removed from the circuit board since that is the usual signal circuit for the fan operation.
    waldolc's Avatar
    waldolc Posts: 5, Reputation: 1
    New Member
     
    #7

    Sep 3, 2009, 10:25 AM
    Gotcha. Oddly enough, after cycling through heat for about an hour and then turning the unit off for 30 minutes, it's working perfectly in A/C mode. Not sure what's going on here but my fingers are crossed.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #8

    Sep 3, 2009, 06:30 PM
    See how it goes and post back with the results.
    waldolc's Avatar
    waldolc Posts: 5, Reputation: 1
    New Member
     
    #9

    Sep 4, 2009, 06:28 AM
    Well, it only works like it should during heat mode. After awhile last night, on A/C the fan stayed on. I'm stumped. The last two techs who came out to my house wanted to charge me an arm and a leg for what they wouldn't tell me. I guess I should find another?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #10

    Sep 4, 2009, 07:31 AM
    With it working corectly in the heat mode we know that the limit control is not causing the fan to run to get you attention since that is a default setting for a overheat condition. So that is OK.

    If you have check all that was requested then I hate to say this but the indicators are pointing to a bad control board. It makes no difference if the board was just replaced or not it still indicates that the board is causing the problem since nothing is left to check. It could be the board was damaged when originally installed? Who knows.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

York Diamond 80 blowing cold air. [ 13 Answers ]

Hi All... Hopefully uou can help me out... I have a york diamond 80 gas furnace. It was working fine up until a few days ago.. It began to blow out cold air when the house clearly was not even close to "requested" temp. It turns on, starts the initial motor, the humidifer also kicks...

Led on york control board [ 2 Answers ]

My furnace blower motor is not working. Capacitor checks good. Outside unit runs. Noticed the LED blinks once, go's off and blower will not come on. All was good last Night. Shaft turns free. Any ideas. Thanks

Diamond 80 York Leaks Water [ 5 Answers ]

My Diamond 80 York central heat and air unit is leaking water under the carpet of the room where the unit is housed. It has saturated the carper in the front of the door to this room. Had repair person come out and he first told me it was the coil and that it was around $700 to replace a coil. ...

York Diamond 90 [ 1 Answers ]

I have a york diamond 90 and I have 4 code show what could it be

"T" sat wiring for york gas furnace control board. [ 3 Answers ]

I have maple/chase programmable "T" stat... Two stat wires going to control board (Note:.. this board operates heat/ac) wire #1 yellow, red, white, green.. wire #2 red, white. Board terminals Y1, Y/Y2, W, R, G, C... What is the correct wiring for wires #1&2 to terminals.. Thanks in advance for...


View more questions Search