Ask Experts Questions for FREE Help !
Ask
    S Jacobsen's Avatar
    S Jacobsen Posts: 7, Reputation: 1
    New Member
     
    #1

    Dec 27, 2008, 07:53 AM
    York 80 Furnace ignition goes off when blower comes on
    I have a York Diamond 80 furnace Model# P4HUAR12N03201A. New construction 05 installation. Went away from this house for 2 months. Came back and furnace won't operate. System ignites, heats up plenum, blower comes on, and then the fire immediately goes out. Has a component failed or has the 2 month downtime created a different issue?
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #2

    Dec 27, 2008, 08:00 AM

    Look for a diagnostic LED through a clear plug in one of the front panels. Is it flashing? Observe the pattern/number of flashes and compare to service label - usually found on one of the panels or on the furnace control board. Post results.
    S Jacobsen's Avatar
    S Jacobsen Posts: 7, Reputation: 1
    New Member
     
    #3

    Dec 27, 2008, 08:38 AM
    Quote Originally Posted by KC13 View Post
    Look for a diagnostic LED through a clear plug in one of the front panels. Is it flashing? Observe the pattern/number of flashes and compare to service label - usually found on one of the panels or on the furnace control board. Post results.

    No flashing.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #4

    Dec 27, 2008, 08:44 AM

    I should have mentioned, check with furnace running. If short-cycle repeats but no LED code is displayed, the thermostat may be the problem. Bypassing the R-W circuit will allow you to check this.
    S Jacobsen's Avatar
    S Jacobsen Posts: 7, Reputation: 1
    New Member
     
    #5

    Dec 27, 2008, 09:34 AM
    Quote Originally Posted by KC13 View Post
    Look for a diagnostic LED through a clear plug in one of the front panels. Is it flashing? Observe the pattern/number of flashes and compare to service label - usually found on one of the panels or on the furnace control board. Post results.

    No flashing.
    MarkwithaK's Avatar
    MarkwithaK Posts: 955, Reputation: 107
    Senior Member
     
    #6

    Dec 27, 2008, 09:49 AM

    Did the system function normally before you left? Was it idle the entire 2 months?
    S Jacobsen's Avatar
    S Jacobsen Posts: 7, Reputation: 1
    New Member
     
    #7

    Dec 27, 2008, 09:58 AM
    Quote Originally Posted by KC13 View Post
    I should have mentioned, check with furnace running. If short-cycle repeats but no LED code is displayed, the thermostat may be the problem. Bypassing the R-W circuit will allow you to check this.
    Thank you very much. The furnace is running with a jumper on the R-W circuit in place. Although the furnace does not run continuously. It runs for a few minutes and then shuts down for a few minutes and then restarts again.
    S Jacobsen's Avatar
    S Jacobsen Posts: 7, Reputation: 1
    New Member
     
    #8

    Dec 27, 2008, 10:00 AM
    Quote Originally Posted by MarkwithaK View Post
    Did the system function normally before you left? Was it idle the entire 2 months?
    Yes. AC worked. Heat has not been used since last March or April and then it worked fine.
    MarkwithaK's Avatar
    MarkwithaK Posts: 955, Reputation: 107
    Senior Member
     
    #9

    Dec 27, 2008, 10:01 AM

    If you jumped R-W and you are still getting the short cycling then your stat isn't the problem. What condition is your filter in? You could be bouncing off the high limit switch.
    S Jacobsen's Avatar
    S Jacobsen Posts: 7, Reputation: 1
    New Member
     
    #10

    Dec 27, 2008, 11:10 AM
    Quote Originally Posted by MarkwithaK View Post
    If you jumped R-W and you are still getting the short cycling then your stat isn't the problem. What condition is your filter in? You could be bouncing off of the high limit switch.
    Filter is new.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #11

    Dec 27, 2008, 11:18 AM

    Still no LED flashing?
    MarkwithaK's Avatar
    MarkwithaK Posts: 955, Reputation: 107
    Senior Member
     
    #12

    Dec 27, 2008, 12:04 PM

    I'm still leaning towards the high limit. Hard to pin it down without actually being there. The coil could be plugged. I would be interested to know what the temperature rise is.
    S Jacobsen's Avatar
    S Jacobsen Posts: 7, Reputation: 1
    New Member
     
    #13

    Dec 27, 2008, 06:54 PM
    Quote Originally Posted by S Jacobsen View Post
    Filter is new.

    FYI Solution found: Burner forced draft system had small particles of debris. Upon furnace restart one small particle partially plugged vacuum hose leading to the safety switch. Blowing out the debris allowed air draft hose connected to the switch to clear and the switch began to function again.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

York Stellar furnace blower problem [ 2 Answers ]

I have a 19 year old York Stellar furnace. Model P1UCD12N04601B 57,000 btu's. This unit was salvaged from a military housing complex that closed in 1990. The unit shows very little wear. All the parts look new. The unit sat no operational for nearly 16 years. I removed the unit from the house...

York Stellar Furnace Heating up Furnace Room to 110 Degress? [ 2 Answers ]

I have a York Stellar Furnace in my newly purchased house. Furnace is 15 years old. Furnace is releasing hot air from front grills and heats up furnace room to 110 Degrees. I had a Bryant Furnace in another house and this never happened. All plenams and ducts are taped and sealed so the heat is...

Blower by york [ 2 Answers ]

I have a york furnace an inotice that the blower is not running strong when the air is no?

York Dimond 80 Gas Furnace, No Blower shut down [ 1 Answers ]

I have a York Diamond 80 Gas furnace approx. 11 years old, and I have a problem w/ Blower not shutting down. Runs constant.. This has happen intermittently, but now it will not shut down at all. Heat works, but once the exchanger cools down the fan still keeps running until the cycle calls for heat...

York furnace - No ignition,no heat [ 4 Answers ]

I have a York Gas Furnace (model# P2MPD14W08001B, 12yrs old) giving out no heat. I did basic troubleshooting and realised system was not igniting; replaced ignitor (changed original 4-5 years ago) - fired up initially and then went out after running for about 30 minutes. I cleaned the flame sensor...


View more questions Search