    Why does my A/C run for as little as a few seconds when the thermostat kicks in
    I have a programmable thermostat. The A/C works runs fine when it's cooling a room from a different tempeture. The [potential] problem comes when it's the A/C turns on to maintain the programmed temp. It then runs for like 8 seconds, then I hear the outdoor condenser unit shut off, then the blowers inside turn off about a minute later. It does this every few minutes. I'm assuming it shuts off because the desired temp. has been reached but the short duration concerns me. By the way, when the outdoor unit turns off, it sounds like a quick half a second grind from the A/C unit closet. Is this normal?

    Age: 6
    Tonnage: 3
    Characteristics: Heat Pump System, Electric
    Condensation: Condensate Pipe To Exterior
    Cooling Testing: Reverse Valve Not Checked, Outside
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Oct 19, 2010, 11:39 PM

    BYpass the thermostat and see if the unit stays running. If so then I would suspect that the thermostat is installed in a incompatible area or the wire that comes through the wall has not been sealed to prevent in wall air migration to cause the thermostat to short cycle OR the thermostat is not setup correctly or is defective.
    timeticker's Avatar
    timeticker Posts: 2, Reputation: 1
    New Member
     
    #3

    Oct 27, 2010, 03:29 PM
    It looks to be the swing on the programmable thermostat was set to .25. I set it to .5 and it seems to have fixed the problem.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Trane TUD XL 80 furnace buner flame kicks out after 3 seconds [ 0 Answers ]

I have replaced the high limit switch and flame sensor.

Pressure switch kicks in and out every 2-3 seconds? [ 3 Answers ]

Have a well - water pressure surges and the pressure switch kicks in and out every 2 to 3 seconds. Thanks in advance for any help!! Bing

I set the temp, heat kicks on for 30 seconds, then shuts off [ 5 Answers ]

I know next to zilch when it comes to my heating and air system, so that's why I'm kind of led to believe this may be something simple. We have natural gas heat for our home. Lately, it's been a little cooler in the day so I've set the thermostat for about 73 degrees and switched the system over...

Furnace kicks in for 5 seconds- shuts off [ 1 Answers ]

My furnace kicks in and shuts off within seconds. Sometimes it does this several time in a row. Sometimes runs perfectly normal. Thermostat fluctuates by 3 degrees as I'm standing there looking at it. Any ideas?

Outside Blower kicks on for 5 seconds then goes off for 10 seconds [ 1 Answers ]

I've looked all over this forum for something like this, but nothing I've see quite nails my problem so If I missed it, sorry. Here it goes... My outside blower comes on for about 5 seconds when my thermostat activates for the heat. With furnace still on the blower shuts off for 10 seconds and...


View more questions Search