    Why does AC compressor fan run on when the furnace runs
    Since replcing the termostat, my AC compressor fan runs when the furnace runs. This never happened before I replaced the thermostat. What did I do wrong with the thermostat replacement?
    WallyHelps's Avatar
    WallyHelps Posts: 1,018, Reputation: 136
    Ultra Member
     
    #2

    Jan 5, 2012, 06:34 AM
    It sounds like you hooked the compressor control wire to the wrong screw. It is usually yellow, or at least the screw is marked Y. Without knowing what you have now, it is difficult to say what is wrong.

    Hope this helps,
    WallyH
    royalmay's Avatar
    royalmay Posts: 2, Reputation: 1
    New Member
     
    #3

    Jan 5, 2012, 12:33 PM
    The Blue wire was incorrectly hooked up to the B terminal on the thermostat. When I traced the Blue wire to the furnace it was connected to the Y termainal in the furnace, when this change was made on the thermostat, it is working correctly again. Many thanks

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Heat pump outdoor fan runs not compressor voltage at compressor good. New compressor [ 1 Answers ]

Have a new compressor. Just replaced fan runs compressor does not, have voltage at the compressor plug? What could stop from coming on high side and low side equal at 100psig.

Can my condenser fan run while my compressor runs [ 1 Answers ]

My condensenser fan would start and stop I removed it from the pressure switch and wired it so it runs when the compressor runs is this OK??

Amana air conditioning compressor fan runs but compressor does not [ 9 Answers ]

I have an Amana Model RCE30A2B Compressor unit installed it is about 6 years old, the compressor will not cut in when demanded yet the cooling fan for the unit does

New Compressor Run OK. HVAC Fan only run in Heat mode. [ 15 Answers ]

This board is awesome. I have done some reading first on here. Here's my case: Compr runs fine. Fan on HVAC blower inside runs only in Heat mode. Not on Cool. Not even on "FAN-ON" as opposed to FAN-AUTO. Can this be an issue with relay and board within HVAC? Per other thread, it was talking...


View more questions Search