    What is the correct way to test an Inducer motor?
    Day & Night FAU, Model # 373LAV48075, get 27volts at R and Common. I tested all Safety switches and pressure swithc. Inducer motor does not come on. Is there a way to test the inducer motor? What voltage should I get at the IND Motor connection?
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #2

    Dec 24, 2009, 07:07 PM

    Should get 110/120v at inducer leads when stat is calling for heat. If no voltage at motor, then problem lies before motor. Try jumping r and w on the furnace control board and see if motor comes on. If it does, then there is a problem is in the thermostat or stat wires.
    jrs_58's Avatar
    jrs_58 Posts: 2, Reputation: 1
    New Member
     
    #3

    Dec 26, 2009, 03:46 PM

    Thanks for the response, I have been in and out of the home; I did check the inducer motor leads with the t stat wire disconnected and with a jumper at Red and white at the control board, I get an brief OL reading on the multi-meter then it reads 1.30v AC
    I also tried a jumper on every flame roll out,high limit,pressure,and draft switches, tested all wires on the harness for continuity; still inducer motor does not come on unless, I connect the 120v directly from the leads going to the control board. (I already replaced the control board)

    Any other suggestions will be appreciated.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #4

    Dec 26, 2009, 03:56 PM

    Try this: open blower access panel & tape interlock switch closed. Listen closely for "clicks" from board. Apply gentle pressure to the square multi-pin connector near the center of the board. If inducer starts, board is likely failing. Inspect for melted solder joints, etc.
    yamvcgz's Avatar
    yamvcgz Posts: 2, Reputation: 1
    New Member
     
    #5

    Feb 25, 2010, 12:29 AM

    What is that square multi-pin connector for?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Goodman inducer motor [ 2 Answers ]

Hi, I live in near Nashville, Tenn. I have a Goodman HVAC unit model PG036100-1B REV E (gas furnace and A/C unit) over 20 years old. It started to make a very loud grinding noise when the furnace came on, so I had it inspected by a local HVAC repair company, and the tech said the inducer motor is...

Matching up the correct capacitor with the correct condenser fan motor? [ 4 Answers ]

How crucial is it to match the right capacitor to the right condenser fan motor? If you have the wrong capacitor, can this cause the motor to stop after running for a while, say 20 or 40 minutes? It would start up again, but would allways stop. The specs for the motor are: Emerson E-line, model no...

What is the inducer motor [ 3 Answers ]

I have a bryant 395C gas furnace and the inducer motor assembly is making noise. The motor seems fine and the furnace operates normally, but there is a plastic wheel attached to the end of the motor that is rattling when the motor runs. I've looked at pictures of many inducer motor...

Inducer motor not working [ 0 Answers ]

I have carrier gas furnace model 58msa, inducer motor is not working. Any answer, how to replace it?

Why does an inducer motor gets blocked [ 1 Answers ]

Why does an inducer motor gets blocked


View more questions Search