    Water leaking from the pvc pipe on Air Handler
    I think the air handler pipe that goes to the outside is clogged, can I use liquid draino in it to clean out the line?
    acetc's Avatar
    acetc Posts: 1,004, Reputation: 79
    Ultra Member
     
    #2

    Jul 25, 2007, 03:21 PM
    The best way to clear this drain line is to blow it out from the air handler to the out side , you may have to cut the line to be able to blow it out, so you will have to couple it back together. Use compressed air or co2.
    Be sure this line goes outside and not to the tail piece of a sink somewhere, if this is the case then lay a wet towel in the sink to keep from blowing STUFF out of the trap and into the room.
    Also go outside and make sure the end of the drain is open and not plugged. I don't recommend Draino. Mike

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Water leak from air conditioner air handler [ 6 Answers ]

How do I stop water from dripping from my air handler? The technician has checked the pans, drains, and freon with no luck. He is stumped as to where the water is coming from.

No hot water to 2nd air handler [ 8 Answers ]

I have a Burnham V8 Series oil-fired boiler and two ADP multi-position air handlers, one in the basement and one in the attic. All the units are approximately six years old. The boiler/air handler combo in the basement works fine, but the attic air handler is not producing warm air. The...

Leaking underground PVC drainage pipe [ 2 Answers ]

Recently water has been pooling on my lawn and spilling over into my neighbor's yard. I think it may be a leaking underground PVC drainage pipe. How can I fix this?

Water Dripping from Air Handler [ 8 Answers ]

I have a newly installed, (maybe four months ago), central AC unit. It is a split system, 3.5 tons, Rheem 13 SEER. Both the compressor and the air handler were replaced. All was working fine until yesterday, when I began hearing a dripping sound coming from beneath the air handler. A quick look...

Air handler leaking [ 1 Answers ]

My air conditioning air handler is located upstairs in my two story townhome. I noticed the air handler is leaking water... it leaks from under the area where you change the filer. I noticed there is no water leaking from the pipe outside. I put a bucket under the unit for now... is this serious?


View more questions Search