    miliu's Avatar
    miliu Posts: 7, Reputation: 1
    New Member
     
    #1

    Jul 14, 2007, 11:30 AM
    Urgent: How to wire VisionPro TH8320?
    I recently bought a new thermostat from Honeywell, model VisionPro TH8320. I'm replacing the old thermostat MapleChase 9620 (now Robertshaw 9620). The old one was working correctly. It has 7 wires. I believe I figured how to wire 5 of them, but not sure about the remaining two. I tried different combinations, but it always gives me heat instead of cold.

    Based on Robertshaw 9620, my configuratioon is a typical heat pump with cool active reversing valve and auxiliary/emergency heat. 7 wires has following code: C (24V common), R (24V hot), Y1 (first stage compressor), E (emergency heat), G (indoor fan), W2 (second stage heat), O (cool active reversing valve).

    Based on this wire, I figured my system must be a 2H/2C system (1 transformer), becase only this one has 7 wires based on instruction of TH8320. Is it right?

    I found the matching terminor at TH8320 for C (24V common), R (Power, with jumper to RC), G (fan relay), W2 (heat relay 2). I connected Y1 (first stage compressor) from MapleChase to Y (cool relay 1). However, I'm not sure with the remaining two wires. E (emergency heat) and O (cool active reversing valve) in MapleChase. I tried to put E into E (emergency heat relay), and O into W (also O/B for 1st stage heat relay or Changeover valve for heat pumps). But I got hot air instead of cool air, although the thermostat says cooling. This doesn't match any wiring guide in TH8320 user manual.

    Please help. Thank you very much.
    acetc's Avatar
    acetc Posts: 1,004, Reputation: 79
    Ultra Member
     
    #2

    Jul 14, 2007, 12:03 PM
    The "O" terminel needs to be wired to the same color wire as the old thermostat was. You will probably have to go into advanced setup to tell the thermostat that you have a heat pump, it will tell you how to do this in the installers guide. Mike
    miliu's Avatar
    miliu Posts: 7, Reputation: 1
    New Member
     
    #3

    Jul 14, 2007, 12:19 PM
    Thank you very much for your help. It looks it's working now. The problem was that I didn't change the advanced setup for System type to 7 for 2 heat/1 cool heat pump (with aux. heat). It was defaulting to 1 heat/1 cool conventional. I'm still not sure if the wirings are completely correct. I'll keep watching it. Thanks again.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Thermostat wiring MapleChase to Honeywell TH8320 [ 4 Answers ]

I have an old thermostat from MapleChase. It has 7 wires and is currently wired as follows: C (black) L (none) R (Red) Y2 (none) Y1 (yellow) E (black) G (green)

Honeywell VisionPRO 8000 Installation [ 5 Answers ]

Hi Everyone! We just finished building our new home and didn't think about thermostats along the way. There is a simple digital thermostat installed at this time but we wanted a programmable one. I attempted to install it today but the compressor wouldn't cut on. I've installed thermostats before...

Wiring for VisionPro TH8320U 2H/1C [ 2 Answers ]

I currently have a York heat pump with a Janitrol gas furnace. Electromechanical 2H/1C with aux heat X=Black R=Red W=White Y=Yellow G=Green O=Orange B=Blue Honeywell VisionPRO TH8320U

BAYSTAT240 to Honeywell TH8320 Conversion [ 1 Answers ]

I am trying to switch my BAYSTAT240 thermostat to a Honeywell vision pro 8000 (TH8320U1008). My old settings were: O: Orange G: Green Y: Yellow X2: Connected to white along with W B: Blue W: (jumpered to U): White


View more questions Search