    Upgrade the blower motor
    Ok, a recent thread mentioned something about upgrading the blower motor. That's exactly what I want to do. My reasons are that, while the air gets cool enough, the flow is just not what I would like probably mostly due to the crappy flex ducts the builders use these days. One solution that has been suggested is to upgrade the blower motor on my Trane. I looked at the furnace and the current blower is already connected to run at the maximum speed on the circuit board so any increased CFM would have to be from either a new furnace, replacement of flex ducts with sheet metal, or new blower.

    Where might I find suitable blower replacements for this Trane air handler? I probably can figure out what the max load the circuit board can handle by looking at the installer handler which I own, but I have no idea how to identify which blower to buy and what will fit in this Trane.

    Thanks,

    - RP
    letmetellu's Avatar
    letmetellu Posts: 3,151, Reputation: 317
    Ultra Member
     
    #2

    Mar 25, 2007, 08:54 PM
    More of a problem than what the circuit board can handle is the amount of air that your AC can handle. When you are running the AC you want enough air going across the Evaporator coil to lower the temp of the air entering the return grill around 20 degrees F. where it leaves the Evaporator coil. Speeding up the air flow will only raise the temp of the air coming out of the duct work. Lowering the speed will lower the temp and if slow enough it can result in freezing tanking place in the Evaporator coil, thereby slowing the air even more and causing more icing leading eventually to a completely blocked evaporator coil.
    It could be that you have too many opening for the amount of air that goes through the duct work or maybe that your system needs to be balanced so that the fight amount of air goes to each room.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #3

    Mar 26, 2007, 04:12 AM
    Your first step might be to look at the coil inside and make sure it is clean and free to cool the air. If it is blocked with a bunch of crud, the air coming out will neither best as strong or as cool as it should be. Then check the differential. It is possible they cut corners on the installation and you don't have enough air flow. It should have been checked and the jumpers set to give adequate air flow. However if the maximum speed you say you are using, wasn't quite enough, the installer may have left it that way hoping for the best.

    If you have a clean coil, no leaks or restrictions in the ducts, the system isn't freezing up, and greater than 20 degree differential, then you may want to look at a higher speed motor. You could get all the data off your current motor and take it to an electrical or HVAC supply and see if they can help you. You could also go to the web site of the manufacturer of the current motor and check for a motor with the physical dimensions of yours, but a higher speed.
    russp's Avatar
    russp Posts: 2, Reputation: 1
    New Member
     
    #4

    Apr 3, 2007, 05:09 PM
    Quote Originally Posted by labman
    Your first step might be to look at the coil inside and make sure it is clean and free to cool the air. if it is blocked with a bunch of crud, the air coming out will neither best as strong or as cool as it should be. Then check the differential. It is possible they cut corners on the installation and you don't have enough air flow. It should have been checked and the jumpers set to give adequate air flow. However if the maximum speed you say you are using, wasn't quite enough, the installer may have left it that way hoping for the best.

    If you have a clean coil, no leaks or restrictions in the ducts, the system isn't freezing up, and greater than 20 degree differential, then you may want to look at a higher speed motor. You could get all the data off your current motor and take it to an electrical or HVAC supply and see if they can help you. You could also go to the web site of the manufacturer of the current motor and check for a motor with the physical dimensions of yours, but a higher speed.
    Good advice. I know the coils are clean as I had them checked at the end of last year to make sure. He also checked the coolant levels and said they were fine. I think part of the problem is the flex duct has sagged in a few areas (I'll fix that). Then I'll measure the air temp to see the differential. If it's poor I'm going to guess it needs more coolant, despite what the last professional said.

    Would there be any real benefit to replacing portions of the flex duct with true metal ducting? The flux duct seems like it just is too easy to restrict air flow given it's lack of a smooth interior.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Blower motor capacitor? [ 20 Answers ]

I've got a Lennox G12 series furnace and the blower seems to have stopped working. I read a few posts and saw a reply mention giving the fan a little push start while the burners kicked on. I did this and the blower started up. I can hear the "current" feeding the motor but it seems to be having...

Blower motor [ 1 Answers ]

THere is no air blowing when the heat is on. The furnace does come on but no air blows. If I turn the heat off and manually turn the fan on the air blows. If I leave the fan switch in the on position and turn the heat on the air stops.

Blower Motor [ 1 Answers ]

I have read multiple posts about wiring for blower motors and saw one that almost answered my question. I have an old blower motor that I would like to convert to a shop air filter. I know that it is a multi-speed motor. It has 8 wire connections and are labeled as such: Power cap cap ...

Blower motor problems [ 1 Answers ]

Hello. I came home last night to find my ac had stopped working. The ac unit runs fine but the blower motor had stopped. I shut the system down and waited till the next day and tried it again. It worked great for about 3 or 4 minutes and then stopped again. The ac unit works but the blower motor...


View more questions Search