    Transformer problems
    Hello newby here
    Having problems with a 40va transformer burning out on an AC unit I'm currently working on. It is an older unit with a fan center/motor control board? (a transformer with a low voltage junction block on top of it and a fan relay mounted next to it.) Complaint was indoor fan not working found had no 24V from xrsfrmr and the back of it looked burned. Replaced the fan center board and new xrsfrmr burned out once again on primary side (OL) on ohm meter. Motor tested fine ran well. My question is since this is obviously a short somewhere should I be concentrating on the primary side circuits or can a low voltage short burn out the primary side? Supply voltage to unit tested OK. Any help appreciated.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    May 4, 2009, 02:59 AM
    Start checking the low voltage circuits for a short or overload condition. Use a small inline fuse holder from radio shack or others to protest the transformer while testing OR get a small resetable circuit breaker device like I have and that way you will not have to keep buying fuses while you are testing.

    Look for pinched/cut wires. Many times they can be in a wall going to the thermostat. Try labeling then disconnecting the thermostat at the furnace/air handler to start with since the thermostat wirng seems to be where many of these kind of problems originate. Happy Hunting.
    mphsrzrbck's Avatar
    mphsrzrbck Posts: 10, Reputation: 1
    New Member
     
    #3

    May 4, 2009, 04:01 AM

    Thank you, I will start there.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #4

    May 4, 2009, 08:27 AM

    A 3 Amp automotive fuseholder on the secondary works.

    I have a post somewhere where I suggest 2 particular automotive lamps in series as the "fuse". When you find the short, the light comes on. Select 12 lamps that draw no more that 40 watts and pu them in series.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

24v Transformer [ 4 Answers ]

I am trying to find a good source for a 24v transformer. I am working on a project that will use a digital home thermostat to control a couple of 24v relays. I've found all of the parts but a suitable, cheap, 24v thransformer. I thought this would be the easiest part to find but it is turning...

Transformer [ 10 Answers ]

Hi I've constructed a velleman amp, 2x30watt output, model K4003. Now to power this you need a 50Va transformer. I bought one and the pins along the input side are labelled 0 120 0 120 and the output 0 12 0 12

A/C Transformer [ 2 Answers ]

I have an older central air conditioner unit that needs a transformer (confirmed by certified a/c repairman). The cost of the transformer through the a/c company was a bit steep, so I did not have the repair made. I am trying to locate the specific transformer that I need and have a friend that...

Transformer [ 1 Answers ]

I have a Goodman Heat Pump. The transformer in the air handler burnt out and I replaced it with one protected with a reset button. Now, when I use unit, I can only use in emergency heat. When I use in heat or cool mode it will trip the transformer in 30 seconds. Is this a low voltage problem? Air...

Transformer Problems [ 1 Answers ]

I recently replaced my transformer about a month ago in a Carrier Heat Pump. It has burnt up again. Any suggestions on what could be causing this? I also replaced the t-stat, could I have wired it wrong? Please help... thanks...


View more questions Search