    Trane xc90 troubleshooting
    My xc90 (the furnace) has sporadically worked on and off for the past couple of years. Right now it's not working at all.. there is 24v at W but the inducer isn't coming on. The error code tells me there is a pressure switch issue but the green led flashes slowly indicating there is no call for heat. If I still had hair, I'd be pulling it out. Help.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Oct 27, 2009, 11:52 AM
    Turn off main furnace power then jump R and W on the low voltage strip in the furnace then reactivate main power and post back with results.
    starlitecafe's Avatar
    starlitecafe Posts: 8, Reputation: 1
    New Member
     
    #3

    Oct 27, 2009, 02:03 PM
    Quote Originally Posted by hvac1000 View Post
    Turn off main furnace power then jump R and W on the low voltage strip in the furnace then reactivate main power and post back with results.
    There is 24v back from the stat to W but the green led flashes slowly indicating no call for heat.
    starlitecafe's Avatar
    starlitecafe Posts: 8, Reputation: 1
    New Member
     
    #4

    Oct 27, 2009, 02:06 PM
    Quote Originally Posted by starlitecafe View Post
    There is 24v back from the stat to W but the green led flashes slowly indicating no call for heat.
    I had disconnected and then reconnected power and even waited 60 minuets to clear the memory. I keep getting the same error code (pressure switches) but even when I bipass them, no dice.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #5

    Oct 27, 2009, 02:08 PM
    I do not care if 24 volts is coming back from the thermostat. I did not ask you that question. I told you to do exactly this for a reason.

    Turn off main furnace power then jump R and W on the low voltage strip in the furnace then reactivate main power and post back with results.
    starlitecafe's Avatar
    starlitecafe Posts: 8, Reputation: 1
    New Member
     
    #6

    Oct 27, 2009, 02:18 PM
    Quote Originally Posted by hvac1000 View Post
    I do not care if 24 volts is coming back from the thermostat. I did not ask you that question. I told you to do exactly this for a reason.

    Turn off main furnace power then jump R and W on the low voltage strip in the furnace then reactivate main power and post back with results.
    Ok. Upon re energizing I had 2 error codes. One indicated pressure switch problem and the other indicated an inducer communication fault.
    starlitecafe's Avatar
    starlitecafe Posts: 8, Reputation: 1
    New Member
     
    #7

    Oct 27, 2009, 03:14 PM
    Quote Originally Posted by starlitecafe View Post
    Ok. Upon re energizing I had 2 error codes. One indicated pressure switch problem and the other indicated an inducer communication fault.
    My mistake. It is an xv90.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #8

    Oct 27, 2009, 03:52 PM
    The next step is to check the pressure switch and inducer motor for proper operation.
    starlitecafe's Avatar
    starlitecafe Posts: 8, Reputation: 1
    New Member
     
    #9

    Oct 27, 2009, 04:41 PM
    Quote Originally Posted by hvac1000 View Post
    The next step is to check the pressure switch and inducer motor for proper operation.
    I removed the hoses and blew into the pressure switches and they appeared to function properly. I put 110v directly on the inducer motor (high speed) and it worked properly. While it was running mysteriously on it's own, which it has done from time to time, the bearing temperature maintained at 165f which seemed normal as the burners were on at the time.
    starlitecafe's Avatar
    starlitecafe Posts: 8, Reputation: 1
    New Member
     
    #10

    Oct 28, 2009, 01:23 PM
    Quote Originally Posted by starlitecafe View Post
    I removed the hoses and blew into the pressure switches and they appeared to function properly. I put 110v directly on the inducer motor (high speed) and it worked properly. While it was running mysteriously on it's own, which it has done from time to time, the bearing temperature maintained at 165f which seemed normal as the burners were on at the time.
    Perhaps someone can tell me if the pressure switches should be no or nc upon a call for heat. Also, does the inducer motor, after a proper time out, supposed to come on first, creating pressure(or lack there of) for the switches, when heat is called for.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Trane XL20i heat pump requires Trane 900 series thermostat? [ 2 Answers ]

Hi, I was wondering if the Trane XL20i heat pump requires the use of Trane's 900 series thermostat or if a Honeywell VisionPro IAQ thermostat can be used.

TRANE vs Amana in New Home: Is a TRANE upgrade worth $4k? [ 8 Answers ]

Background/Details: Building new home in North Texas. Closing at end of August. Builder and I are in dispute over what hardware to install for the AC. House is gas heated so this is about the AC side only. The AC hardware that comes with the house is made by Amana (under license to Goodman...

Trane XL14i 410a leak troubleshooting [ 2 Answers ]

I have a 410a leak with my Trane XL14i system. The leak has been there since the installation. Each season they need to add 410a. I have a HVAC company doing the troubleshooting for me. One of their techs told me that a Trane XL14i system shouldn't use dye to perform the troubleshooting....