    Thermostat wiring for system change
    My AC went out of my Mobile Home, It was a unit incorporated with the heat system. The heat still works fine. I bought a cooling unit that is an all in one unit and tapped into the supply line for the vents and ran a return but I am having problems with the thermostat wiring. How do I need to wire the Thermostat differently to run the AC unit or do I have to install another thermostat?:confused:
    wmproop's Avatar
    wmproop Posts: 3,749, Reputation: 91
    Ultra Member
     
    #2

    Jul 8, 2009, 08:27 AM
    Need to know what kind of tstat you have,for starters, brand and model number
    Is it heating/cooling or heat only?
    How many tstat wires do you have?
    What kind of (brand) a/c unit do you have?
    Do you have gas/electric/oil furnace?
    lakeviewpastor's Avatar
    lakeviewpastor Posts: 4, Reputation: 1
    New Member
     
    #3

    Jul 8, 2009, 10:26 AM

    Thermostat is Hunter 44100B, It it a Heating and Cooling. It has 4 wires Green, Yellow, Red, and White, There is also a blue that is not connected. The AC unit is a Coleman and the Furnace is Electric. Thanks for help
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #4

    Jul 8, 2009, 01:33 PM

    This sounds like your using the old heating system and the new cooling system and would like to use a single thermostat.

    With two systems, that usually means two transformers and the use of a stat which has Rc and Rh separated rather than jumpered.

    Also, some moble homes, specifically Coleman may have had a switch at the furnace to switch from AC and Heat. Does yours?

    All of this complicates things, if true.
    lakeviewpastor's Avatar
    lakeviewpastor Posts: 4, Reputation: 1
    New Member
     
    #5

    Jul 8, 2009, 02:47 PM

    The original system had both heating and cooling. I am still using the heat but the compressor went out on the cooler. I could not afford to replace the whole cooling system which was what a pro told me needed to happen. I purchased a used self contained cooler. All I need to do is hook up the thermostat so that I can switch to cooling and turn on the new cooling unit. Right now the thermostat is jumped from RC to RH. I don't know of any switch at the furnace to switch between heat and cool.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #6

    Jul 8, 2009, 04:20 PM

    If your cooling system has a 24 VAC contactor that needs to be supplied power to turn it on, then all you have to do, is connect the Y (call for cool) lead of tsat to one end of the contactor.

    The other end might be problematic to find. It's the other side of the secondary that does not go to W (call for heat). Again, assuming the 24 VAC turns on the heating system.

    G (fan) may be required too. Not sure if your using the same fan as the heating system for AC.
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #7

    Jul 8, 2009, 04:21 PM

    Honestly, your best bet here is to install a separate thermostat for the cooling unit. Keep it completely separate from the funace and you will have no problems. When you get the new stat, make sure it is a cool only stat. This will simplify the wiring.

    One note, most people get rid of the separate cooling system in exchange for a central air system(which you had). I would have replaced the condenser before installing a separate cooling system. I would keep my eyes open for a used condenser to get your setup back the way it should be.
    lakeviewpastor's Avatar
    lakeviewpastor Posts: 4, Reputation: 1
    New Member
     
    #8

    Jul 10, 2009, 05:54 AM

    I got the unit going. I put it on its own thermostat, the problem now is it won't quit. It doesn't shut off, woke up this morning to a freezing cold house. It even runs when the thermostat is turned off.
    wmproop's Avatar
    wmproop Posts: 3,749, Reputation: 91
    Ultra Member
     
    #9

    Jul 10, 2009, 09:47 AM
    Either you have a wire on the wrong spot, or possibly you have a stuck contactor,
    But if both the indoor airhandler and the outside unit doesn`t cut off its probably a wiring prob.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Did I buy a wrong programmable thermostat for bryant heat/ac system? Wiring confusion [ 8 Answers ]

We've been in this house for 25 years now and have had the same heater/ac/thermostat. Lately, I've been looking for ways to cut energy costs and so I bought a programmable thermostat (hunter #44550) based on good reviews. After I read the manual, I attempted to remove the cover plates to our...

Wiring diagram change from Addison Thermostat to a Honeywell [ 4 Answers ]

Can someone answer what the w3 wire would need to be hook to on the new Honeywell RTH7400 5-1-1. we are removing a addison thermostat which runs a Gas furnace and a heatpump. Please help with wiring diagram

Wiring direction for a multi wiring system thermostat! [ 3 Answers ]

I have a 2 wire system (3 phase), need to connect multi wiring system thermostat! Need to know if, its correct to just use line#1, and the device already has a jumper?

Thermostat change with old system with Y1, W1 and W2 [ 3 Answers ]

I currently have a Honeywell Chronotherm III thermostat which I believe came with the house. I'm trying to replace it with a Honeywell 5-1-1 Day (RTH7000 Series) programmable thermostat. After I disconnected the old one and started the new one, I got to a point where it says "If your old...

NO HEAT! Janitrol heat pump and AC system. Changing to Lux Thermostat. Wiring issue. [ 11 Answers ]

I have a Janitrol A/C and heat pump system. I replaced the thermostat with a Lux T9000LC The A/C works fine, but the heater does not. I have it wired as follows: G - Green Y - Yellow W - White RH - Pink B -


View more questions Search