    Thermostat - Honeywell to Hunter - Condo - Not working."
    Hello...

    I am trying to replace an old Honeywell T8195B with a Hunter 44110. This is located in a condominium with the A/C unit on the roof and the fan and elec. Heating unit in the ceiling. I have located the thermostat wire in the ceiling and it is split and wired as indicated in this image.

    http://farm1.static.flickr.com/162/3...c67a1d86_o.jpg

    I have reviewed many postings and just can't get this to work. When I re-install the old Honeywell thermostat everything works so I have not done any damage to the system.

    Can anyone help? Thanks.
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #2

    Feb 1, 2007, 02:25 PM
    Looks like you have a heatpump, but the new thermostat is not for a heat pump.
    basil1211's Avatar
    basil1211 Posts: 4, Reputation: 1
    New Member
     
    #3

    Feb 1, 2007, 04:08 PM
    I have confirmed that I have a heat pump. The Hunter 44110 and Honeywell RTH230B that I have are not compatible with a heat pump. Now I know what a heat pump is. Live and learn. Thanks for the help.
    basil1211's Avatar
    basil1211 Posts: 4, Reputation: 1
    New Member
     
    #4

    Feb 1, 2007, 04:10 PM
    Maybe I am wrong after reading your edited post. Can you have an all electric heat pump?
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #5

    Feb 1, 2007, 04:24 PM
    Quote Originally Posted by basil1211
    Maybe I am wrong after reading your edited post. Can you have an all electric heat pump?
    Heat pumps are all electric, just a fancy airconditioner. Put an electric heat pack in the air handler, and now you have electric aux/emergency heat with your heat pump.
    basil1211's Avatar
    basil1211 Posts: 4, Reputation: 1
    New Member
     
    #6

    Feb 1, 2007, 04:25 PM
    Yes, it looks like you can.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Help to replace thermostat Honeywell T841a for Hunter 44155c [ 1 Answers ]

Hi, I am trying to replace my T841a 1712 Non-Programmable Heat Pump Universal Thermostat for a Hunter Model 44155C, but I can't make the new unit work.:confused: The Honeywell thermostat has the following connections: Color Cable Terminal Blue -----> X Red -----> W2 ...

Hunter To Honeywell Thermostat [ 1 Answers ]

I recently purchase a Honeywell RTH6300B to replace a Hunter 44402 problem is there are only two wires coming out of the wall one White and One Black where do these wires go on this Honeywell? Thanks JIm

Thermostat Replacement Honeywell 890121 - Hunter 44110 [ 2 Answers ]

Hi there! Need help to replace an old Honeywell model 890121 with a Hunter 44110 My existing (Honeywell 890121) wiring: Brown - C Green - G Yellow - Y --jumpered to--W Red - R White - O Hunter 44110:

Need Help - Getting "No AC Power" with Hunter Thermostat [ 2 Answers ]

Installed a new Hunter Thermostat today and I am getting "No AC Power". So I looked in the fuse box and the 5V that connects the Black and Red wire was blown. I since replaced the fuse with a new one and it also blew. Please help. It gets pretty cold at night.

Wiring question replacing Honeywell thermostat w/Hunter [ 0 Answers ]

I am replacing an old standard Honeywell thermostat (model T8034C) with a Hunter programmable digital model 44110. I have a 5-wire system. The wires are color coded and the Honeywell labels match the wire colors. Those are: White, Yellow, Green, Orange, and Red. THe only labels on the...


View more questions Search