    Thermostat fuse blows when heat pump is turned on to heat mode only
    Heat pump won't work in heat mode... blows fuse in thermostat every time . A/C works fine. Disconnected white wire for heat at outside unit and did not blow fuse... wire shorted?? Please help
    Grady White's Avatar
    Grady White Posts: 1,417, Reputation: 59
    Ultra Member
     
    #2

    Feb 11, 2016, 09:34 PM
    It certainly sounds like a shorted white wire. It's easy to find out by simply swapping the white for another color if there are any unused wires.
    The problem could also be a short outdoors in a wire only powered in the heating mode. One that comes to mind is maybe going to the reversing valve if the valve is 24v.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Heat pump blows 3 amp fuse [ 1 Answers ]

Recently we had a bad storm in Florida after the storm I noticed the 3 amp fuse keeps blowing when turning the stat to heat. I have a carrier model FB4C any advice for a novice would be much appreciated.

Heat pump never turns on, handler blows continuous with no heat except with AUX heat [ 2 Answers ]

10 year old Rheem air handler RHBA-21J8MFCA, 1/3HP, 2.8A. New WeSt Columbia, SC 29170, Model 2HP13L48P-1B, HCFC-22, 4TON. Installed new out of box iN July and AC working splendidly but start-up is "violent" and loud. Installer says I need some sort of "start-up kit". I put off as had planned...

Rudd heat pump work OK in heat mode but not cooling mode [ 1 Answers ]

Rudd heatpump that use r410 refrigerant pressure OK in heat mode but pressure low in cooling mode

Heat Pump blows 5amp fuse when switching between defrost & back to heat. Them Heat work [ 3 Answers ]

I have a Carrier Heat Pump System. It’s about 5 years old and has functioned OK until this Christmas Eve. One problem is the condensing unit is not kicking back on after it goes into defrost mode. I found a 5AMP fuse blown in the attic unit and once replaced it functioned. At least for a day or two...

20 yr old Lennox heat pump fan blows constantly in heat mode [ 5 Answers ]

20 year old Lennox heat pump - outside temps been 30's at night, 40's daytime UPDATE: I went outside and the unit is covered in frost on 3 sides! I've been reading on Google about frosted heat pump units and can't determine how to manually defrost it. Apparently, the auto defrost is not...


View more questions Search