    May 15, 2005, 03:24 PM
    Thermostat
    I am trying to install a new digital thermostat to an existing RUDD system. The original RUDD thermostat is currently installed. How do I find out how to install the thermstat? The wiring diagrams do not match the wires I have installed. And how do I find out what type of system I have for air conditioning? Thanks. Paul
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #2

    May 15, 2005, 07:32 PM
    Usually there is a 24 volt AC transformer in the furnace with the secondary winding connected to a red wire running to the thermostat and a blue wire to the gas valve, A/C relay, and fan relay. From the thermostat there will be white wire to the gas valve, yellow to the A/C, and green to the fan. The thermostat is wired to switch the power from the red to the white, yellow, and green as needed with the blue completing the circuit. It may be wired to have the control wires return to the furnace and its controls and then a second wire goes to the A/C unit. Internal wiring may replace the green wire if the thermostat does not give you the option of fan only or continuous fan.

    The new thermostat may have a RC terminal the old one didn't. Usually it is jumpered to the R terminal, red wire. It may also have a terminal marked B or C. There will also be a terminal at the furnace marked B or C. Connect them using a blue or black wire if there is one in the cable.

    As long as the air conditioner has an outside unit controlled by a relay, it doesn't much difference what kind it is. It needs to have a pair of wires running from the Y and the B or C terminals at the furnace, out to the relay coil.

    You may have W1, W2,. at the furnace or thermostat making provision for different heating rates. Unless you can figure out something different from the installation manual, try connecting the white wire to W1.
    pauly001's Avatar
    pauly001 Posts: 2, Reputation: 1
    New Member
     
    #3

    May 16, 2005, 03:27 AM
    Thermostat
    Labman,
    That is exactly right. I am trying to figure where I need to hook the W2 X amd E. E and W2 are umpered so I figured that was my power. Wrong the red is. This is where I got the mix up. The new thermostat has RH RC jumpered and E and W2 jumpered. I have a RUDD system with the thermostat. I have a DICO Thermostat I am trying to install.as long as I get the power right and follow the instructions to the typical 5 wire installation? I thank you for the help.
    Paul
    I tried to upload pictures of each thermostat but they are too large. If you would like to see them I can send them any way you would like. Thanks again.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Do I need a new Thermostat? [ 1 Answers ]

:( Here’s my problem: I have a basic thermostat. It's the one that has the needle on the right side. I set it to 78 deg. And my AC unit will not turn off until it reaches 74 deg.'s:confused: Then when the temperature gets to 76 deg.'s my AC starts back up again! :eek: (hence with out the...

New thermostat -- no a/c [ 2 Answers ]

Hi, We just replaced our thermostat. Seemed simple enough -- 4 wires, red, white, yellow, green. There is 24 V between red and all the others at the thermostat. When we set the temp to cool, you can hear the switch in the thermostat click, but no air comes out. It seems like the thermostat...

Thermostat [ 1 Answers ]

I have two Maple Chasee (Robershaw now)thermostats in my house controlling two separate rooms. Recently one thermostat stopped turning heater on, but still working on cooling. My other thermostat worked fine both on cooling and heating. I bought a new Robershaw 9600 and replaced the old Maple...

Help with thermostat [ 1 Answers ]

I just turned on the heat for the first time and I noticed that the lights for emergency heat and the Aux heat are on constantly... Its not really cold outside, like the low 60's. Is there something I can do, cause if all that is running, its going to overload my electric bill? Please help ...


View more questions Search