    Rheem Furnace Fan Control Center Transformer
    I was replacing my transformer/fan control center for a Rheem Furnace (central Heat/air) and did not label the wires. I am now very confused... I have two sets of contact wires coming out of the relay, one set "no" and the other "nc". And the Primary wires on the transformer... How do I connect this to my furnace??
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #2

    Dec 5, 2006, 08:45 PM
    connect the common, x-former hot, and 120 line together. Connect the X-former neutral, (usually the blower motor neutral) and the line neutral together. NO goes to fan high (cooling speed) and the NC usually, goes to the fan limit control, then that goes to the blower low (heat speed)

    Always double check the appliance has no power before working on it.
    skip bertrand's Avatar
    skip bertrand Posts: 3, Reputation: 1
    New Member
     
    #3

    Dec 1, 2008, 03:51 PM
    I am looking for wiring diagram for a rheem model # 32080CDA5 gas furnace

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Fan Control Center Wiring [ 5 Answers ]

I'm trying to make this old Magic Chef furnace work in my garage. I got it and the Fan Control Center was broken, laying inside unwired. I have no wiring diagram for this unit but the M# is G76-7502 C2-5. I need help wiring the fan control center and the fan limit switch to power. I bought a new...

Fan Center Transformer burned [ 7 Answers ]

My fan center transformer failed, I replaced it with a new one, and it has failed too. It seems the transformer burns out when the thermostat is moved to the cool setting. There must be a short in the low voltage wiring, however I'm unsure of what I should see across the different L.V. wires...

Fan Control Center Wiring [ 12 Answers ]

Hi, I have an oil forced air furnace, with the fan controlled by a Honeywell L4064 fan limit control. The fan itself is capable of two speeds. I would like to add a fan control centre so that I can control the fan from a switch, hopefully able to select speeds. I gather adding a White-Rogers...

Looking for control wire on transformer [ 5 Answers ]

I am installing a new HONEYWELL T8601D2019 - it won't power on. I realize it needs a control wire connected to the C... I can not figure out which wire off my transformer is the control. I have three blue wires, a red, black, and white. Red, black and white are all connected to the unit in...

Honeywell thermostat heat/cool in Rheem 2 stage furnace? [ 1 Answers ]

I have a Honeywell 1 Heat/1Cool thermostat (TH6110D1013) that I would like to use with a Rheem 2 stage gas heat furnace. I think it is possible but would I get the same benefits as having a thermostat with 2 heat/1 cool? Would I just connect the W terminal on the Thermostat to the W2 on the...


View more questions Search