    Rheem 90 Classic
    For the last month or so my two year old Rheem 90 Classic model #RCGA-36A2GG21XI condensing furnace keeps cycling on for a minute, the flame lights up, the fan comes on and then it turns off. A minute later the same thing happens for about 5 times. Then all of a sudden it works fine. A couple of weeks ago we changed the themostat because we thought that was the problem. It has been working sporadically. What might be causing this?
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #2

    Jan 10, 2009, 04:29 PM
    Locate and observe the status LEDs when this is occurring. They should be visible through an oval-shaped viewer in the blower access panel (2 green, 1 yellow). Note the pattern, then check the service label/troubleshooting chart on the inside of the same panel.
    moongirl2421's Avatar
    moongirl2421 Posts: 8, Reputation: 1
    New Member
     
    #3

    Jan 10, 2009, 05:02 PM
    Thanks for your reply. I see first the 2 green lights are on, then 2 green with orange flashing, then the orange goes off (along with the flame), then the green light on the left stays solid and the right one flashes.
    I have checked the troubleshooting panel but it's kind of hard to make heads or tails of what that means.
    My husband has been worried because the pvc pipe which goes out of the roof does not have a cover on it. It has been snowing pretty hard and he's wondering if the water gets in there.
    Thanks for any advise.
    Sue
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #4

    Jan 10, 2009, 05:20 PM
    Where is the unit located? Check the vent pipe for sags that might be accumulating water. By design, the pipe should slope downward toward the unit so any moisture will run back.
    moongirl2421's Avatar
    moongirl2421 Posts: 8, Reputation: 1
    New Member
     
    #5

    Jan 10, 2009, 05:24 PM
    The furnace is located in a closet. The pipe pretty much goes straight up. We were able to get the furnace to fire and stay on by turning it up to 90.
    It is running now-the two green lights are on and the orange light is blinking slowly.
    moongirl2421's Avatar
    moongirl2421 Posts: 8, Reputation: 1
    New Member
     
    #6

    Jan 10, 2009, 05:25 PM
    It was installed two years ago and has worked fine the last two winters.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

NO HEAT Rheem Classic 90 series 3 years old [ 6 Answers ]

I have a Classic 90 Series Rheem RGRA series upflow/downflow furnace 3 years old. Intermittently, the furnace will not flame up or give out heat. Sometimes it only blows cold air. Sometimes, it locks out (middle green light flashing once then pausing). The furnace repair company came out and...

Rheem HVAC classic 90 that will not light [ 2 Answers ]

I have a Rheem HVAC classic 90 that will not light The electronic igniter will not lit the burners I have changed the igniter and still will not work I can light the burners with a match but when it gets to temperature it will not light for the next cycle

Rheem Classic 90 duct cleaning [ 1 Answers ]

While I had the blower of my 10 year old updraft Rheem 90 HVAC system removed for inspection and cleaning, I noticed that above the fan in the duct there is a coil with black, gooey, fibrous material coating it on the bottom, which sloughs off easily. Is this an accumulation if dirt that should be...

Rheem Classic Clicking [ 1 Answers ]

I have a problem with my outdoor Rheem Classic 9 Heat Pump I just reciently changed the fan control relay, after a week of running it seems to be clicking. I problem I had before with the relay was it would not turn the fan. I can tell the clicking is coming from that relay. I don't know if...

Rheem Classic 90 Plus Blower start issue [ 11 Answers ]

The blower started acting up for few weeks. There was a several consistent short rumblings of the blower, something like half second on and half second off after ignition. Once the rumbling is over, the blower fan just works fine. I can also hear the relay inside the control box clicks when it...


View more questions Search