    STL_Jeff's Avatar
    STL_Jeff Posts: 3, Reputation: 1
    New Member
     
    #1

    Feb 18, 2011, 02:20 PM
    Recently replaced furnace control board, now blower will not come on with AC.
    I recently replaced a 50A50-110 control board (Comfortmaker) with a White-Rodgers universal 50M56U-843 control board and the furnace worked fine throughout the winter. However, I just tried the AC for the first time this season and the blower will not come on with the AC. The compressor and outside fan seem to come on as they should. Could I have a couple wires hooked up incorrectly on the conrol board? Any help would be greatly apprectiated. Thanks in advance.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #2

    Feb 18, 2011, 06:40 PM
    It's a three speed blower control make sure you have a blower speed wire on the cool term on the board. Make sure you have a good connection on the G terminal on the control board(thermostat wire) from the thermostat.
    STL_Jeff's Avatar
    STL_Jeff Posts: 3, Reputation: 1
    New Member
     
    #3

    Feb 18, 2011, 11:03 PM
    Quote Originally Posted by STL_Jeff View Post
    I recently replaced a 50A50-110 control board (Comfortmaker) with a White-Rodgers universal 50M56U-843 control board and the furnace worked fine throughout the winter. However, I just tried the AC for the first time this season and the blower will not come on with the AC. The compressor and outside fan seem to come on as they should. Could I have a couple wires hooked up incorrectly on the conrol board? Any help would be greatly apprectiated. Thanks in advance.
    It's a three speed blower control make sure you have a blower speed wire on the cool term on the board. Make sure you have a good connection on the G terminal on the control board(thermostat wire) from the thermostat.
    STL_Jeff's Avatar
    STL_Jeff Posts: 3, Reputation: 1
    New Member
     
    #4

    Feb 18, 2011, 11:07 PM
    Comment on STL_Jeff's post
    Well I'm VERY new to forums, so I hope I update this the proper way. Thank you T-Top, it seems as if you were correct. I had hooked the new control board up exactly as the old one was hooked up. The problem was, there was a red wire coming from the blower that was hooked to "Park" on the old control board, but needed to be hooked to "Low Heat" on the new control board. I'm guessing this is because this new board has the ability to control multiple speed blowers and my old blower is just one speed? Whichever reason it is, it works and I'm happy. More importantly, the old lady's happy:) Thanks a lot for your help, it's much appreciated!

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

45692-001 blower control board will not turn blower on in either heat or cooling mode [ 2 Answers ]

Armstrong G1N80 furnace blower control board will not turn on fan at all. Not in heat or cooling mode. I can hear a click when fan should be energized, but no fan startup. Pigtailed the fan hot and neutral,and fan works fine. Is this just a blower control board problem, or something else? We had...

I have a bryant 397h furnace and the blower will not shut off.replaced circuit board [ 2 Answers ]

I have a bryant 397h furnace and the blower will not turn off.I replaced the control center circuit board and still runs. Any suggestions?

Does the board control blower timing and shut down on rudd furnace [ 1 Answers ]

Myfurnace runs too long blowing cold air, does the card control the time or is there another device that does the yellow light blinks

Dual fuel rheem furnace not working, defrost control board replaced still not working [ 1 Answers ]

Hello there, I have a Rheem furnace and is only one year old. Recently my furnace didn't come on so I had someone come out and look at it and it turns out it was the defrost board on the heat pump that was bad. I replaced the board with a new one and turned the system on and it worked on heat and...


View more questions Search