    R134a in an R22 system
    What would the effects be if an r-22 system were to be evacuated and filled with R134a?
    What is the reason that this equipment can not handle this gas?
    rickdb1's Avatar
    rickdb1 Posts: 185, Reputation: 15
    Junior Member
     
    #2

    Aug 29, 2006, 05:05 PM
    The boiling points of the 2 are completely different.(-15 for 134 and -41 for R-22). In order for the system to maintain the correct temps/pressure, the refrigerant must be compatible. 134 A operates at higher pressure/temps than R-22 and will not cool, as the pressure in the system is directly related to temperature.
    juggallojed's Avatar
    juggallojed Posts: 165, Reputation: 10
    Junior Member
     
    #3

    Sep 4, 2006, 11:25 AM
    Quote Originally Posted by rickdb1
    The boiling points of the 2 are completely different.(-15 for 134 and -41 for R-22). In order for the system to maintain the correct temps/pressure, the refrigerant must be compatible. 134 A operates at higher pressure/temps than R-22 and will not cool, as the pressure in the system is directly related to temperature.

    Very good answer but the kicker for me is the polyester oil used with the 134a its not compatible with the mineral oil used with r-22 systems.. turns it into sludge..
    AirZonehvacr's Avatar
    AirZonehvacr Posts: 13, Reputation: 1
    New Member
     
    #4

    Aug 11, 2008, 05:02 AM
    ISCEON 59
    R417A Advantages
    • The only HFC based R-22 replacement that is compatible with both synthetic and mineral oils (MO,AB,POE).
    • Proven compatibility with all standard equipment components and materials used in R-22 manufactured systems.
    • Suitable for use in scroll, screw, rotary and reciprocating compressors.
    • Closely matches R-22's operational pressures.
    • Can be used in a wide range of traditional R-22 temperature applications, and beyond, while providing adequate oil return and system capacity.
    • Avoids the need for unnecessary oil changes and only requires minor system adjustments or modifications.
    • Zero ODP (ozone depletion potential) HFC refrigerant.
    • Improved COP (coefficient of performance), NU-22 has a lower global warming impact compared to R22, as indicated by NU-22's TEWI (total equivalent warming impact) measurement.
    • Non-toxic and non-flammable (ASHRAE classification A1).
    • Compatible with all standard refrigerant oils, NU-22 can drastically reduce the level of waste oil handling and disposal normally associated with using refrigerants requiring an oil change.
    Performance Specs:
    Boiling point
    -41.8°C (-43.2°F)
    Critical temperature
    90.5°C (194.9°F)
    Critical pressure
    559 psia
    Density (saturated vapor)
    @ boiling point temp.
    0.2447 lb/cf
    Density liquid @ 25°C (77°F)
    72.85 lb/cf
    Heat of vaporization
    @ boiling point temp.
    89.42 BTU/lb
    Quality Specs:
    Max. moisture
    0.001%vol
    Max. non-condensable
    1.5%vol
    High boiling impurities
    0.01%vol
    Safety Specs:
    ASHRAE designation
    R417A
    ASHRAE safety classification
    A1
    Max recommended exposure limits
    1000 ppm
    Refrigerant - NU22 (R417A)
    Part
    • Compatible with all standard refrigerant oils.
    • ASHRAE Designated.
    • R22 like operating characteristics.
    • Exceptionally Low TEWI.
    10% Energy Reduction Over R22.
    • Zero Ozone Depletion.
    • No Expensive Retrofits.
    • Can Be Topped Off Repeatedly.
    • ASHRAE Rated A1.
    Non Toxic - Non Flammable
    Vette3's Avatar
    Vette3 Posts: 2, Reputation: 1
    New Member
     
    #5

    Feb 8, 2011, 04:22 PM
    Can an R-134A AC unit be installed with a drained, flushed, and evacuated EXISTING R-22 evaporator coil?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

DX System [ 2 Answers ]

Detailed design details of DX System

System [ 3 Answers ]

Dear sir, I have a problem in my system i.e. it reboot automatically after some time interval. I have checked all the possibilities that solve this problem but I can't found the proper result. So please help me for solving this problem. ...

How do I increase H2O pressure on well system with a water filtration system? [ 2 Answers ]

Howdy, I would like to know how I can increase my water pressure. My current system uses a well pump with a small pressure tank, and "D" control valve. It then runs through a WATERSOFT filtration tank, RAINSOFT water softner, and on the Hot water side, an AQUASTAR on demand hot water system. I...

New System [ 4 Answers ]

Does anyone have a suggestion for minimum specs for a new business PC? Small business running Office and Quickbooks and tons of pictures for reproduction, Adobe Photoshop? Want a screaming desktop! I have one in mind, but am unsure of myself.


View more questions Search