    dobes49's Avatar
    dobes49 Posts: 10, Reputation: 1
    New Member
     
    #1

    Aug 3, 2010, 09:54 AM
    Plenum sweating profusely
    The plenum above my basement installed updraft Gibson KG6RC furnace in cooling mode is sweating profusely. Cooling seems to be working fine, and drainage tube from plenum seems to be draining normally, but I worry that the condensation on the outside of the plenum will rust the furnace out as it seems to filter its way down the outside and through the cabinet to the floor surrounding the furnace. Should this plenum, be insulated? If yes, should I use foil-faced urethane and glue it to the plenum?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Aug 3, 2010, 10:22 AM

    High humidity in the basement will cause this to happen. When the moisture hits the cool plenum it condenses. Insulating the plenum will be a big help in preventing this. Also make sure the drain is running free and if push comes to shove a dehumidifier installed in the basement will help remove the moisture that is causing the problem.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Do I need to replace the plenum [ 2 Answers ]

I am in the process of replacing my old furnace with a new high efficient Carrier. The existing furnace is about 35 years old and is still working but not really well. I have received several quotes, mostly from large HVAC companies. One quote is from a smaller shop but they come with good...

HOT plenum causes short cyle ? [ 1 Answers ]

System ( +25 yrs ) is short cycling. Sound at cold air returns closest to furnace sounds like someone sucking for air ( my Dad had COPD and it sounds like him.) Contractor observed: Plenum super hot on the blower side; plenum much cooler on side nearer to panel. Blower motor dirty....

Maytag fridge on fritz sweating profusely [ 1 Answers ]

I own a Maytag (top freezer) refrigerator model number MTF2456AE... bought in 2001. In the past 3-4 months it has started sweating profusely - but specifically on the freezer door. Today I found out the condensation is coming down all four sides and I have puddles in the front on the ground. ...

Drainage Plenum for new plumbing [ 14 Answers ]

Is it sufficient to have a single 4 inch vent for a bath, a toilet and a sink draining into the sewer line from the main floor of our house to the basement sewer stack and is the placement of the vent important in the plenum (see web page: http://web.mac.com/pughimag2/iWeb/Site/Library.html

Plenum EMT Bushings? [ 3 Answers ]

I'm installing a wireless access point in a commercial environment on a drop ceiling. The space above the drop ceiling is plenum. The data jack for the access point is installed in an electrical box through a ceiling tile supported by a rod snapped onto the ceiling grid. I want to have the data...


View more questions Search