    Outside unit does not start
    When A/C comes on the evaporator blower comes on but neither the compressor or fan outside start. Got 120 at each leg on line side of contactor. Every 20 seconds or so the contactor buzzes for several seconds then stops (trying to start compressor, I guess) and is humming continuously. Figure it has to be contactor or dual capacitor. Any way to know for sure? Capacitor looks normal, no bulges or splits. Thanks in advance for your thoughts on this.

    denman
    wmproop's Avatar
    wmproop Posts: 3,749, Reputation: 91
    Ultra Member
     
    #2

    Jun 22, 2011, 11:03 AM
    Did you check breaker in breaker box,, sounds like you have low voltage (24volts) coming from furnace but maybe no high voltage (230V),, just a thought
    denman's Avatar
    denman Posts: 48, Reputation: 2
    Junior Member
     
    #3

    Jun 22, 2011, 03:07 PM
    Didn't bother checking at panel as I had 240 at the cut off switch next to outside unit, I have 120 volts on each leg of the contactor inside the unit.
    wmproop's Avatar
    wmproop Posts: 3,749, Reputation: 91
    Ultra Member
     
    #4

    Jun 22, 2011, 06:45 PM
    Comment on denman's post
    OK,, didn`t see that(probably there) in the first note,sorry, so now is the contactor engaged by low voltage? If so do you have the same high voltage coming out the other end, 120 volts at each leg?, if you do you could still have a bad capicitor, they don`t always show up bad just in looking,, you might remove and take it somewhere to have it tested,
    denman's Avatar
    denman Posts: 48, Reputation: 2
    Junior Member
     
    #5

    Jun 23, 2011, 08:25 PM
    Wrproop,thanks for the responses.
    I do have 120 one both load legs. I'm going to take capacitor to get tested. Thanks again

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

In-hom smart start breathalyzer unit [ 7 Answers ]

I have an in-hom breathalyzer for taking breath samples three times a day. During the final test of the day, it read 'viol'. I am not sure why this happened. I went back and was reading through the informational pamphlet I received and it said to walk away from this was admitting guilt. I quickly...

Sears Kenmore Dishwasher start button won't start unit [ 0 Answers ]

I have a Kenmore Ultra Wash dishwasher that will not start when pushing the start pad location. It will pump when put on the Cancel/Drain button, but will not start after that. It does have power, or the pump would not run during the Cancel/Drain cycle. The washer was purchased in Jan 20, 2006...

Rheem Classic 90 A/C unit noise at start up only [ 3 Answers ]

I have a Rheem Classic 90 , 3 years old . Started my a/c unit today and it made a noise at start up only . It was something like rrrrrrrrrrrrr, for a brief second , stopped and ran just fine after. Anybody have any clues what this might be.

Outside unit will not start and humms [ 1 Answers ]

Yesterday after returning home I noticed the upstairs unit was not cooling. Checked the breakers and noticed they were not blown. Inspected outside compressor area and noticed no freezing on the coils and fan not blowing. Turned system off for about an hour and then restarted system. Outside...

A/C unit does not start [ 8 Answers ]

I have a lennox A?C unit installed model #10ACB30-5p. It's a 10 year old unit. It was working fine until last Saturday when I noticed that the blower is blowing hot air. I checked the unit outside and the Fan and the compressor were not running. I shutdown the thermostat and re-started it and the...


View more questions Search