    My nordyne will not heat up
    I have a nordyne model#e2eb-015ha,s/n e2e9807-14487,electrical power supply 240 vac
    I can cut it on to heat when it come on it blow out cold air is this something I can fix myself need help
    Grayfurnaceman's Avatar
    Grayfurnaceman Posts: 1, Reputation: 1
    New Member
     
    #2

    Jan 13, 2012, 10:29 AM
    I assume this is an electric forced air. Electric furnaces are composed of several elements. These elements are usually sequenced on by time delay relays. The first element comes on with the fan 10 to 20 seconds after the thermostat is calling for heat and the other elements come on with a further time delay. When no heat is coming out but the fan is coming on, the first and easiest thing to look for is breakers off. Many of these furnaces have more than one breaker. Breakers are usually installed both in the furnace and in the breaker panel. Breakers to be tested should be turned off then back on. Next is burned wires on the controls. These controls are inside the covers of the furnace. A visual inspection will tell you if this the problem. Remember when you are working inside the furnace, there is lethal voltage. Before opening, turn off all breakers! A voltage tester is an excellent investment to be sure. If there are burned wires, replace with stranded wire using terminals from the hardware store. All connections should be very tight! Loose connections will cause overheat of terminals. If all looks OK you probably have sequencer failure or open elements

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

My Nordyne Heat/AC won't heat and the blower keeps running [ 1 Answers ]

I have a Nordyne Model GR4GA-024k072C gas heater. The Blower runs constantly no matter what thermostat setting and its not producing any heat. When I took off the cover it has a red light flashing. Was wondering how to go about figuring what's wrong. Thanks in advance for any help.

Nordyne Propane Furnace - no heat [ 3 Answers ]

I have a Propane furnace model # KG6RC-060C-12A. The furnace fires up but shuts off after a few seconds. It attempts this 3 times and then shuts off. The code light is blinking 4 times. I checked the wiring for loose grounds and it appears to be OK. The unit is only 3 years old. Any...

About my Nordyne Heat Pump [ 0 Answers ]

I recently got a Nordyne installed. How can I find out if it is a 14 seer and a 2.5 ton?

Nordyne Gas heater no Heat [ 13 Answers ]

I hope some one can help me. I have a Nordyne gas furnace, only about a month old. I installed it myself and everything worked fine for the first few weeks. Now there is no heat. The first time this happened, I turned on the heat and the blower turned on immediately along with the exhaust vent...

Nordyne heat pump high suction in heat [ 1 Answers ]

I have a 2 yr old heat pump.in heat mode at 40 deg outside I have 120 psi on the suction and 160 psi on the disc. 99 deg. At discharge from condenser.first season for heat.sounds like a stuck or leaking reverse valve. Any suggestions. Thanks ps I tried switching from air to heat a few times


View more questions Search