    Nordyne Furnace "burner limit circuit open", during A/C operation
    Hi all, Hope this makes sense and required info is present. Any help or suggestions is appreciated, thanks.

    Furnace brand is Nordyne, about 3 years old, cooling portion model# of unit is JS3BA-036KA. This issue started last week. The A/C still works, but now the blower portion? Doesn't shut off most times. Opened the panel and the LED blinks in correlation to "limit circuit open or external load on "W". Tried jumping all connections in line to the blower to get it to stop, but no avail. Any tips/troubleshooting I can run through? Would the circuit board need to be replaced? Or am I missing something simple? The unit has been nothing but trouble since I moved into the house 2 years ago, not that that really helps... ;) Thanks, again.

    Paul
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Sep 9, 2007, 04:59 PM
    Turn of all electric power to the furnace. Then turn back on. See if this resets the board. If not find the limit and jumper it and reset the board by turning off the power again. If not trace the w wire from the thermostat to the board and checks for shorts. If not the board could be defective.
    pawwright's Avatar
    pawwright Posts: 3, Reputation: 1
    New Member
     
    #3

    Sep 9, 2007, 05:08 PM
    Thanks - turning off the power worked a for the first few times earlier in the week - now no go - will do on tracing the wire, thanks again. I'll try to jumper the limit that is the upper limit one that is flat against the firewall and reset the power.. It seems to have multiple limits -- is that possible? This is a power vented furnace if that makes a difference.
    acetc's Avatar
    acetc Posts: 1,004, Reputation: 79
    Ultra Member
     
    #4

    Sep 9, 2007, 05:31 PM
    Any one of the limits could be causing your problem, look for a reset button on the limits , it may be a very small button between the wires of the limit, you may also have a limit on the blower housing, good luck. Mike
    pawwright's Avatar
    pawwright Posts: 3, Reputation: 1
    New Member
     
    #5

    Sep 10, 2007, 04:40 AM
    OK, thanks - I will check out and follow up, thanks again.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Desktop shortcut to open " import export wizard " [ 2 Answers ]

Does anybody know what to type in the new shortcut box to create a desktop shortcut to import export wizard ? Typing in " import export wizard don't work " Kadillack

Brayant 80t furnace, 'Limit or flame rollout switch is open"? [ 1 Answers ]

HI, I am new here and am having a furnace problem. As a new homeowner I would like to take a look at this myself before just grabbing the phone books. I have a Bryant 80t furnace. Built in 2000 and has been serviced every other year. Unit is clean and in good shape. Woke up to a cold house and...

Furnace "burner limit circuit open", How to fix? [ 2 Answers ]

The furnace in my vacant rental property does not light. The blower runs but the igniter never glows and the gas valve does not open. The LED blinks once which means the burner limit circuit is open. How do I replace the burner limit circuit? Inside the furnace cover I found the electronic...

CD Rom & Burner Drives not listed in "My Computer" [ 8 Answers ]

I am hoping you can help me "reset" my drives. A few days ago I could not use my CD Rom drive nor burner as neither would read a CD. I went into the systems folder in the control panel and disconnected both from the device manger. I did this because there was a yellow icon over each drive and...


View more questions Search