    Nordyne. E1EB-015HA
    Nordyne model E1EB-015HA How do I check the sequencer's and limit switches what are the omh's values or what should be open or closed on the bench, I have the furance and coils on the bench for testing.
    Unit blows transformer in service. Was great before I cleaned the cooling coils above the furance. I got water in the furance below. I have cleaned all componets. Suspect the sequencer's or limit switch. There is a short for sure-- it blows the transformer in about 60/90 seconds. AC unit on the outside of house runs for about one minute and shuts down. Heating coils have contiunity no breaks with meter and visiual

    Help
    billg
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    May 18, 2008, 12:39 PM
    IF you can get to the sequencer with enough room for testing voltage and feel comfortable doing so, test across M1/M2, M3/M4 and M5/M6 after waiting 2 minutes from call of heat by t-stat.

    You should read 0 vac across all 3 sets and it should remain that way for a few minutes as home warms up

    NOTE you have a low voltage short in order for the low voltage transformer to blow. Add a inline fuse to the transformer so the fuse blows during testing and not the transformer.

    I would look or sound out all low voltage wires. It could be a short in the wall or a short going to the outside unit.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Nordyne heater [ 3 Answers ]

Indicator Light blinking twice shows pressure switch is open will not allow blower or heat to work.

Nordyne LED blinkin codes [ 5 Answers ]

Can someone give me the codes for all the Nordyne LED blinks? My furnace was blining 4 times, I replaced the igniter and now it is blinking 2 times... All the codes would be greatly appreciated - thanks, in advance. :cool:

Nordyne furnace trouble [ 2 Answers ]

I have a Nordyne furnace, and the furnace got stuck in it's cycle. The vent blower would come on and that's it, so I had the circuit board replaced. Now, the a/c works but the furnace cycle won't even start. The light on the board just blinks twice. Any help would be great. Thanks.

Nordyne e2 electric furnace with ac [ 1 Answers ]

Hello I have an nordyne e23h012hn electric furnace, the control board is burnt and evaporator fan will not come on, replaced board and it burnt up to. The circuit on the board that burnt is the common line voltage to the fan, could it be the fan motor shorted causing this problem . Thanks chris ...

Nordyne heater fan not working right [ 1 Answers ]

I just moved into a 1991 mobile home with a heater of the same age. The furnace is a Nordyne Intertherm model MGHA 056ABFC-01 Forced air and natural gas heater. The problem is with the fan I turn the thermostat up to turn the furnace on. Once the burner heats up the fan turns on, The fan...


View more questions Search