    No gas supply, or faulty valve in gas fireplace?
    We use a regency Gr55-3 ~20,000btu gas fireplace for heating our bedroom. Its about 10 years old and has given us no trouble before.

    The gas supply line is a small (3/8"?) flexible copper tube that runs about 40' from a prv. I believe the prv lets pressure down from 2psi to a few inches of water.

    This year when I first turned it on for heating season, everything appeared to work although the gas valve in the fireplace took a few tries with the thermostat before it finally opened. About a day later, the pilot light was running at about half its normal flame height, and the main burner would not come on. Now there is no gas coming out the pilot light when I try to light it.

    Is this a prv problem (i.e. no gas) or a gas valve problem at the fireplace? Any sensible way to troubleshoot?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Nov 19, 2007, 09:42 PM
    I would start here first at the prv.
    rtw_travel's Avatar
    rtw_travel Posts: 347, Reputation: 36
    Full Member
     
    #3

    Nov 20, 2007, 10:26 AM
    Thanks. Turns out the PRV was fine... I forgot we supply the BBQ off the same PRV, and the BBQ has lots of gas.

    I cleaned up the gas supply valve and the rest of the fireplace and things seem to be working again. Plus I re-aimed the pilot light a bit so the flame was directly on the thermo-thing. I think there was not enough heat on the thermo-thing to keep the pilot light going.
    rtw_travel's Avatar
    rtw_travel Posts: 347, Reputation: 36
    Full Member
     
    #4

    Nov 22, 2007, 06:46 PM
    The pilot light went out again... but now I'm sure I fixed it.

    Initially I thought it was the thermopile (the electronic gizmo that turns the pilot gas off if the pilot light goes out.). However my local fireplace store was nice enough to give me some information. If a multimeter reads 325mV or greater across the terminals when the pilot light is lit, then the thermopile is fine. Mine was reading >400mV, so that was not the problem.

    So next stop was the pilot gas line. The pilot gas tube runs from the gas valve to the pilot light burner. At the bottom of the pilot burner is a small orifice about the size of a pin. You need to remove the pilot gas supply line to get at it. It turns out this was mostly plugged. A quick shot of compressed air and its completely free.

    The pilot light flame is now about twice as high as it used to be and all is right with the world again.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #5

    Nov 22, 2007, 09:06 PM
    A plugged orifice will also give the impression of a out of gas situation. Glad you got it going.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Faulty Gas Appliances Warning. [ 1 Answers ]

From http://www.dmu.ac.uk/study/student_services/accommodation/safety_home.jsp The site is for students, but the advice is universal. Gas Safety There are two risks associated with faulty gas appliances, leaking gas and carbon monoxide poisoning. A gas leak should be detectable by the...

Maytag gas dryer, replacing gas valve coils [ 5 Answers ]

Hi, I hope someone can help me. My Maytag gas dryer's igniter glows but then no flame appears. I believe it is the gas valve coils that are bad, so I purchased a replacement kit (3 coils). The instructions say to match the colors of the wires, but my replacement kit has red, black, white...

Gas Piping Question about gas fireplace [ 5 Answers ]

Hello all, I'm not sure whether to ask this question in the heating forum or here, but it seems to be more a piping question. I am installing a gas fireplace. I got it used, and pieced it together from two sources, meaning I'm needing to change a few things. The burner I got was configured...

Gas line to a gas fireplace [ 1 Answers ]

I have an existing gas fireplace place in my home that I moved 1'0" to the right. There is a copper tubing with a shut off and then flex tubing connecting to the fireplace. I am trying to add additional copper tubing on to the existing so I can extend everything to reach the new location for the...

Gas Fireplace [ 5 Answers ]

Hi, I just bought a ventless propane gas log set. I, however, only have natural gas in my household. Is there a way I can convert the propane set to natural gas? Thank you


View more questions Search