    dieseldinosaur's Avatar
    dieseldinosaur Posts: 1, Reputation: 1
    New Member
     
    #1

    Jun 1, 2011, 09:53 AM
    New install rudd a/c question?
    4 ton rudd 410 a/c installed by me a certified tech with an epa license. Freezes up once every six to twelve months. Supply duct sizing is adequate and it has a 24"x24" return should be adequate. Coil is clean and filter. All motors and compressor functioning correctly when freeze up starts. Abnormal finding I can not get the low side pressure above 105 psig which correlates to 32-34 degrees Fahrenheit. This is why I think when there is a slight temp change outside it's just enough to freeze it. If I try to charge the high side will continue to go up but the low side stays the same. My thought are possible restriction in the txv or maybe not enough air flow to the coil. I have tried removing the filter and changing the blower fan speed. Still the problem persists. Supply air is at 48 degrees Fahrenheit and return is around 70 Fahrenheit. New copper was used on install that was properly sized. Any help is appreciated.
    seblewongel's Avatar
    seblewongel Posts: 1, Reputation: 1
    New Member
     
    #2

    Jun 2, 2011, 08:36 AM
    Career
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #3

    Jun 2, 2011, 04:26 PM

    From the info you posted, I would definitely start with the txv. Also could be restricted drier filter. Im assuming the system was purged with nitrogen while brazing, and vaccumed to at least 500 microns. With 410a, if the system is not purged with nitrogen durning brazing, it is likely the txv, or filter drier, or both are partially plugged.

    If everything was done correctly, then I feel your pain, as these symptoms can be a real bear to figure out. Wish you the best of luck, and please do let me know what you find.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Rudd ac questions? [ 1 Answers ]

I have a new rudd air handler and 4 ton compressor, when the unit turns off there is a slight grunt noise. Installer says there is an electric brake on the blower at shut down ,this sounds good but is it true noise is not very loud ?

Rudd furnace [ 4 Answers ]

The flame sensor is clean, but won't ignite. Fan just runs. No heat

Howard, Rudd? [ 1 Answers ]

So, perthians, sand gropers, banana benders, and the rest of my fellow australians, and any others who have an opinion What do you think? Labor or liberal? Howard or rudd? Is a union heavy labor party something to worry about? Has peter garret lost his passion? Do you think we should take the...

Rudd System [ 6 Answers ]

I have a brand new Rudd central air system. Worked great for the first month and a half. Now the condensing unit will cycle on and off in 20-30 second intervals. I checked the breaker and all connections. Is there maybe a high pressure switch that I may be missing?

Question on install of basement shower, tiled walls, prefab base [ 4 Answers ]

I'm in the process of installing a 36in sq shower in my basement. Please let me know if this process is correct: 1) frame out surround, 2x4s, spaced 36in for base to fit, drain and plumbing run 2) put shower base (w/ drain installed) down onto concrete (do I need to put some mortar or anything...


View more questions Search