    Main blower sometimes starts and stops in Gas Furnace
    Hi,

    I got a problem with main blower in gas furnace. I've checked this site, but didn't find an answer.

    Symptoms: Sometimes it starts and stops when burns work or don't start at all. Relay clicks to start blower in 30 seconds after burner started, but blower doesn't start or stops and then tries to start again. And interesting, when I turn heat off on termostat, then blower starts and works for about 3 minutes as expected.

    Furnace details: Model: Goodman GMP 075-3 '95. It has hot surface ignitor and electronic timers to start and stop main blower.

    All parts are original. Air filter was replaced. Sequence works as expected until main blower (inducer fan on/off, burner on/off.) Squirrel cage can be turned by hand easily with no power. I've tried to test capacitor with ohmmeter, it always shows infinity.

    Any advise will be appreciated.

    Thank you.
    hvacservicetech_07's Avatar
    hvacservicetech_07 Posts: 1,083, Reputation: 75
    Ultra Member
     
    #2

    Dec 2, 2007, 11:56 PM
    Try switching the thermostat fan switch from Auto to ON, will it stay running now?
    mik333's Avatar
    mik333 Posts: 3, Reputation: 1
    New Member
     
    #3

    Dec 3, 2007, 04:36 AM
    Tried: blower seems to run Ok in ON position.
    mik333's Avatar
    mik333 Posts: 3, Reputation: 1
    New Member
     
    #4

    Dec 5, 2007, 08:58 PM
    It looks like there was a problem with run capacitor.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Delay-off for furnace main blower when using A/C [ 12 Answers ]

Re Lennox G23Q2/3-75-2 with HS25-311-1P A/C: The built-in delay-off for the blower works well with the furnace, but there seems no easy way to set up a delay-off for the blower when using the A/C. Right now I've connected the low blower wire to the CF terminal on the BCC2 blower control. This...

Main blower fan on furnace [ 1 Answers ]

Hi, I have a high efficient furnace(carrier 58msa). The furnace will not fire up. The house fan comes on first. The inducer fan should run first and then the required sequence should then follow. I have checked the thermostat, it is OK. The other thing I need to check is the pressre switch. I am...

Inducer starts, but blower/furnace never fire [ 6 Answers ]

My furnace suddenly stopped working today. The thermostat triggers properly, and the inducer fan starts running, but furnace never fires and the blower doesn't come on. If I turn the blower on manually at the thermostat, it runs fine. The furnace is an older Payne/Carrier natural gas/forced air...

Only in AM, gas furnace stops and starts [ 1 Answers ]

Hello I have a Gaffers-Sattler furnace, about 40 years old. Runs great, but for one problem. In the morning around 5 or 6, I turn on furnace and it will heat up and run for about 5 to 6 minutes then stop for about 3 minutes and repeat this all morning long. (frustration as this is when its...

Furnace-Yellow terminal not connected-A/C starts stops [ 3 Answers ]

I have a 1988 Rheem RGDA-125-ER furnace. I noticed over the summer that the A/C, when switched to cool, would come on and then immediately switch off if the set temp was higher than the room temp. If I programmed the set temp far below room temp and then switched on, it would run normally and I...


View more questions Search