    Luxaire Central Air Conditioner - ACCLIMATE - intermittent problem
    Hello.
    I have a three year old Luxaire Central Air Conditioner - ACCLIMATE - Model# AL3A036F1A with a YORK Air Handler Model# N4AHD14A06A. It is connected to a White-Rodgers thermostat Model# 1F90-71 (transformer = 24VAC secondary voltage)which is also connected to a hot water base board heatings system with a 2 TACO zone valves. The second zone valve is controlled by another White-Rodgers thermostat.
    The problem I am having is intermittent. When the thermostat turns on "COOL" the air handler fan (inside the house)comes on and the outside air conditioner comes on and cools the house. Then, after it has been off and comes back on only the air handler fan comes on and the air conditioning unit doesn't come on. I went outside to look at the unit was off and the fan wasn't spinning. This happened a couple of days ago (and once last year near the end of the Summer)but it running fine now. I want to be ready when it happens again. What steps should I take to troubleshoot this? Can I rule out the thermostat since the air handler fan turns on?
    Any help would be appreciated.
    Bob
    pdr4d's Avatar
    pdr4d Posts: 5, Reputation: 1
    New Member
     
    #2

    Jul 11, 2011, 07:03 AM
    I found the problem:
    The central air unit outside was working all day then later that day the thermostat called for it to Cool the house and the outside unit did not come on but the air handler did as usual.
    1. I measured to make sure the 24VAC was at the outside unit and it was there (across coil)
    2. I measured the 220VAC input to the contactor and read approx. 240VAC
    3. I measured the output of the contactor (which should be the same as the input 240VAC) and it was not there.
    4. During measuring the voltage,I noticed the contactor pick up and drop out (an the unit wnet on then off). I tapped on the contactor and it stayed on and worked until the next day when I could purchase a new contactor.
    5> Purchased a new contactor and installed it and it has been running ever since (approx 10 days) without any problems.

    Note: I took the contactor apart and found that the contact on the secondary side and pitted so badly that a piece of it fell off. I must have fell off in a spot where it couldn't fall out completely so it would make contact whenver it was in the right spot (therefore tapping the contactor must have moved it to make contact). Would have done me a favor if it would have just fallen clear of the contactor all together.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

My central home air conditioner is blowing cold air but making a loud noise [ 2 Answers ]

My central home air conditioner is blowing cold air and seems to be running fine however all of a sudden it began making a loud noise inside like a Hummm, HUmmm, HUmmm noise when running. Should I expect this thing to die?

Central air conditioner [ 2 Answers ]

The above {heat pump} unit will run outside but the blower will not kick in on the inside. What could be the cause

Central air conditioner [ 2 Answers ]

I have a central air conditioner and I guess for at least 3 days my system hasn't been working properly I had the thermostat set at 72 and the house was at 75 so I went out side and the fan was not blowing at all other parts seem to be OK. I turned the system off for a few minutes and then turned...

Central Air-Conditioner [ 1 Answers ]

I need help, when I turn on the central air, hot air blew out from the vents, and the outside a/c unit did not spin. A contractor came out and told us that the compressor is not working. We have a 35 years old Carrier central a/c, the contractor suggested that we should replace the whole central...

Central Air Conditioner [ 1 Answers ]

:confused: My fan to the air conditioner outside doesn't come. There is air coming out of the vents in the house, but no cold. What should the thermoset be set on in order for the fan to come on outside?


View more questions Search