    Limit switch shuts down system
    I have a 31/2 ton twin pac on a 1700sgft house. Two BRs are not used anymore so I closed the registers to concerve. Recently (last 1 1/2 yrs) the Heater has shut down (Hi Limit sw) twice. My question is, am I causing the limit switch to shut the system down because I closed off two registers (2 ea 6" ducts)?
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #2

    Nov 22, 2010, 03:30 PM
    It is possible and also note, you may be blocking the return air. The system is like a big closed tube, except for leakage, and blockage or pressure buildup will raise the plenum temperature. What temp is the hi limit set at? I'd look at that and also at least crack the doors where the heat is off to allow pressure to equalize.
    jimk77's Avatar
    jimk77 Posts: 2, Reputation: 1
    New Member
     
    #3

    Nov 25, 2010, 09:59 AM
    Thanks ma0641 - I had to reset the HLimit, but this time I opened all vents and doors. I was surprised how much air volume I had closed. I agree with you that there was a significant BACK PRESSURE problem causing the HLimit to protect the system. Thanks again... so far everything is fine!!
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #4

    Nov 25, 2010, 10:22 AM
    Comment on jimk77's post
    Glad to help. You can "tip" me by checking Yes-is this helpful? Brian

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Limit switch [ 1 Answers ]

What does a limit switch do in a furnace and would it not allow the gas burners to come on?

Goodman limit switch/pressure switch? [ 2 Answers ]

Hi, I've got a goodman furnace (mod. # GHT070-3) it's about 5 years old. Recently, the heat will only kick on for about 30 seconds then shut off. It's giving me 4 flashes: Open limit switch, then it kicks off. After that it gives me 3 flashes and turns back on (pressure switch). It seems the...

Limit Switch ? [ 1 Answers ]

My forced air electric furnace will not kick on when the temp drops to the thermostat setting.If I click on the fan all it does is blow cold air . My meter says its 135* but still no heat Please help !

Limit Switch - Pressure Switch [ 0 Answers ]

Hello Folks, This weekend I've been playing with a heating system at my new apartment and I'm trying to figure out what the different componets do. I kind of followed the circuit but still have some missing links... 1-There are some terminals on the furnace's circuit board labeled LIMIT. The...


View more questions Search