    rxfire's Avatar
    rxfire Posts: 2, Reputation: 1
    New Member
     
    #1

    Feb 4, 2008, 07:13 AM
    Lennox G20 gas furnace fails to start the fan
    My Lennox G20 gas furnace ignites the pilot light and starts the main burners. The burners burn normally for about 2 minutes and shut down without the blower fan starting. If I manually set the blower fan to run continuously, the heater cycles on heats the house to the temperature set on the thermostat and shuts down.

    I'm guessing there is a sensor or controller problem, probably which ever costs the most.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Feb 4, 2008, 07:58 AM
    Sounds like the motor blower relay or the fan control is defective. This makes the limit control shout off the flames because the blower is not working. When you turn the fan to manual the blower runs and all is well.You might look in the sticky notes in the beginning of this board to see what those parts might look like. Or you can use your local HVAC contractor that deals in Lennox to see if they have the part you need.
    didle's Avatar
    didle Posts: 2, Reputation: 1
    New Member
     
    #3

    Jun 26, 2010, 10:22 AM
    I have a Lennox G20Q2E-75-7 furnace. The blower fan won't automatically turn on when we turn on the AC or fan only. It does automatically turn on when the furnace is on heat. Help please.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    Jun 26, 2010, 11:24 AM
    Sounds like a problem with the blower motor relay which on most later units is located on the circuit board in the furnace.

    Your service manual

    http://0190acd.netsolhost.com/manuals/G20_Series.pdf
    didle's Avatar
    didle Posts: 2, Reputation: 1
    New Member
     
    #5

    Jun 26, 2010, 11:59 AM

    So if that is the problem, we need to replace the BCC board in the furnace?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #6

    Jun 26, 2010, 01:21 PM
    Quote Originally Posted by didle View Post
    So if that is the problem, we need to replace the BCC board in the furnace?
    IF that is the problem then more than likely the control circuit board is defective. Naturally the board should be tested to be sure it is defective before replacing if you have the knowledge of how to test the relay.

    Another item to check is to make sure the thermostat is sending the signal to the board to start the fan motor when in the A/C mode. I always like to try all other possibilitys before replacing an expensive circuit board.
    MrFixAll's Avatar
    MrFixAll Posts: 1, Reputation: 1
    New Member
     
    #7

    Nov 2, 2010, 06:58 AM
    Possible sensor problem or maybe your motor, it has a capacitor on the side that may
    Fail first... easy fix...

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Lennox Pulse Gas Furnace? [ 5 Answers ]

I am having a diagnostic "nightmare"... only due to lack of knowledge of the Lennox Pulse. This is a roughly '90 model. 80,000 BTU... The problem: Furnace lights for about 10 sec- 2 minutes... shuts down... It resembles a primary air problem, sounds of the fire sucking air. A previous tech just...

Lennox pulse furnace fails to remain started [ 1 Answers ]

I have a Lennox G21 pulse furnace installed in 1993. The unit will start to pulse briefly - maybe 5 seconds or so, and then shut off. We've had two service calls recently. On one call they replaced a flapper, and on the other call did the pressure test, which passed. I've done a visual...

Furnace fan fails intermentantly [ 1 Answers ]

Bryant force air furnace, Model 394GAW036100, This is an old furnace. Circulation fan fails to start intermittently (most of the time) when on auto. Fan runs fine in manual mode. Burner comes on but appears to cycle rather shortly. I know that the limit controls the upper limit of the burner....

Why does my gas-furnace not run? (fan-blower won't start) [ 4 Answers ]

Hi Why does my gas-furnace not run? (fan-blower won't start) I could not see any blown fuses or circuit-breakers; power-switch is on; I ignited the pilot-light and turned the temp to 90 in thermostat - but fan-blower did not start at all, even after waiting for 10 min; I measured voltage at fan...

Condenser fan fails to start intermittently [ 1 Answers ]

Condenser fan sometimes fails to start (notably after its been running for some time). After I de-energize the unit for ~ 1/2 hr, it it then starts up. 1. Do I need to replace fan and capacitor? 2. The installed capacitor has 3 leads with a resistor across 2 terminals. Do I find a like...


View more questions Search