    Lennox A/C Problem
    We have a Lennox HVAC, electric. Probably at least 25 years old. We were having a problem when using the electric heat with breakers popping off. We had the unit looked at. The repair guy said we needed a bigger breaker which we installed. The heat worked fine. When we switched to A/C the fan blowing the air into the house would not turn off. The A/C compressor would turn on an off but the fan kept running and would begin blowing hot air into the house. We got the repair guy back and he of course said he fixed it. He said that the previous guy changed some wires around. Then after a few weeks we heard this terrible noise. It was the fan that blows air over the coils. My husband oiled it and the noise stopped. Shortly there after we noticed that the compressor was once again kicking off but the fan would keep running and hot air would start coming through the vents. When my husband looked at it he noticed that the fan which draws air in from the outside and blows it over the coils was not running when the hot air was coming through the vents. We would turn the unit off for about an hour and then when we restarted the A/C it would blow cold air. Sometimes for hours but eventually it would start blowing hot air. We also noticed that if we try to run just the fan during this time to circulate air in the house by putting the A/C-Heat button to off and putting the fan to on, nothing happens. Is it the motor for the fan that blows air over the coils? I read about some type of transformer, could it be that?

    We of course know that we have more then gotten good use of this unit. But it heats and cools as long as this fan is running.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jun 10, 2006, 06:49 AM
    The breaker that has been changed must match the wire size, not just the amp load. I question the size of the breaker, ask the repair man what is the size breaker, the size wire, and the amp load. This must be confirmed to be sure the load is not larger that the wire can handle, if the breaker size is not matched to the wire, your amp load may be to large for the wire, and if the breaker is too large, there is a potential hazard with the wires heating up.

    The operation issues you mention all seem to be a problem with controls, i.e. the control wiring and the thermostat. The transformer porvides the 24 volts for the control system, it either works or it does not.

    Ask the repair man to check the control system wiring and thermostat for proper operation. You should not need to experience the problems you are having.
    jimarctic's Avatar
    jimarctic Posts: 1, Reputation: 1
    New Member
     
    #3

    Mar 2, 2008, 07:27 PM
    I would agree that you need to look at the t stat. Also look for a new ac contractor. This is a very common issue. The breaker size should be sized by the KW heater you have . Example would be a unit with a 5 kw heater should have a 30 amp breaker. It's aprox 4 amps for every 1 kw of heat.

    Good luck
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #4

    Mar 2, 2008, 07:42 PM
    You may have a blower or run capacitor bad which may be the reason for the breaker throwing at first. A bad blower motor or capacitor will cause high amp draw the motor will over heat and not work at all.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Lennox A/C unit won't run [ 4 Answers ]

Hey all, I'm hoping to get some pointers. I noticed last week that while the fan on the inside unit was running in my house, the outside Lennox (HL26 I think) was not running at all. I usually don't try to fix this kind of stuff myself, so I called a local HVAC/Electric company to come look at...

Lennox Thermostat [ 1 Answers ]

My old lennox thermostat has 8 letters o-g-y1-r-l-t-c-w1-.my new honeywell thermostat has 9 locations lettered rc-r-o/b-y-g-c-l-e-aux.where do i put the l wire from the old lennox thermostat?

Lennox air handler fan always on after inspection [ 1 Answers ]

I just had my HVAC system inspected by a local contractor and after he left today (friday) the air handler is constantly blowing, whether the thermostat has fan set on "auto" or "on". The hander is a Lennox CB30M-65-1P connected to a heat pump, Lennox HP26-060-9P. I also tested each system state...

Lennox home ac [ 1 Answers ]

My central heat and air is making a loud rumble when turned on. It is the inside unit, not outside the house. The lights flashing say the limit control may be open when these lights are flashing, but I am not sure what that is. I think it is the bearings, but am unable to oil, and am not very...

Lennox ac shuts down intermentantly [ 1 Answers ]

I have a Lennox system that is four years old. Recently, after a pwr outage, both of my thermostats have had the pwr light go out and the system does not work, except for the blower continuously running. The weird part is if I leave it alone after a few hours the system starts working again, and...


View more questions Search