    eddiein PA's Avatar
    eddiein PA Posts: 3, Reputation: 1
    New Member
     
    #1

    Sep 25, 2012, 10:51 AM
    Johnson furnace company bellevue Ohio
    I have an older Johnson Furnace Co furnace in one of my units, I recently have a problem with the heat. It seems to go through the process with spark and fan etc but it won't light. It's an older model 48 HWC. Where would I start to testing this unit? And if I were to find the issue would parts still be available?

    48000 BTU
    M-48
    S-K6
    Grady White's Avatar
    Grady White Posts: 1,417, Reputation: 59
    Ultra Member
     
    #2

    Sep 25, 2012, 07:35 PM
    If the spark lights a pilot & the pilot lights the main burner, the pilot orifice is likely clogged. You will need to remove the pilot burner & clean the orifice. Spiders commonly build nests in them & block the gas flow.
    eddiein PA's Avatar
    eddiein PA Posts: 3, Reputation: 1
    New Member
     
    #3

    Sep 26, 2012, 05:39 AM
    The pilot doesn't light, I do see sparking but no flame. I took off the flame sensor to clean as well as the pilot orifice. I will install them back into the furnace today to see if that helps but if the pilot doesn't light, where would I try next? Thanks
    eddiein PA's Avatar
    eddiein PA Posts: 3, Reputation: 1
    New Member
     
    #4

    Sep 26, 2012, 05:47 AM
    Thank you, the pilot doesn't light. I did remove the flame sensor and pilot tube to clean and will install back into the furnace today. As mentioned I do hear and see sparks but no lighting at the pilot. Where or what would I test next?
    Grady White's Avatar
    Grady White Posts: 1,417, Reputation: 59
    Ultra Member
     
    #5

    Sep 26, 2012, 06:43 PM
    Did you remove the pilot orifice & clean it? If not, you need to do so before reinstalling. Dirty pilot orifices are the #1 cause of the problem you are having.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

York furnace Johnson controls error codes [ 0 Answers ]

I have a 13 yr old York Diamond 80 gas furnace with a Johnson Contol board. After running for some time the system shuts down and won't come back up. The error code is solid on. If I power cycle the breaker switch the unit comes right back up. Is this error code that the controller is failing? BTW,...

Foster Johnson gas furnace will not "fire up" [ 1 Answers ]

Our Foster Johnston gas furnace will not "fire up" on it's own. We have to "flip" the breaker switch or toggle it off & on with a switch that has been installed behind the heater. When it does finally "fire up" it will "cycle" twice and then back to point A. When we flip the switch it sometimes...

Johnson & Johnson Co what method do they use [ 2 Answers ]

The question is - What method does Johnson & Johnson uses - Indirect for direct method base on there financial statements?

Gas furnace/burners not working (Fraser Johnson V1000 [ 2 Answers ]

Hi, I recently moved in to a condo with a Fraser Johnson Model V1000 HVAC system. It's probably over 20 years old. The cold air works great but the heat doesn't. The pilot is lit, the fan works, vents are clean, but the burner is not kicking on so only cold air is coming out. Also when I...

Bellevue University [ 1 Answers ]

Hi, I am planning on Attending Bellvue university on line. Does any one have a suggestion or recommendation. Is this credible Thanls


View more questions Search