    Intertherm electric furnace
    I have an Intertherm E1EB-015HA electric furnace I recently had A/C Relay problems with it and since it is 10yrs. Old I thought I would just rebuild the whole thing. So I replaced the sequencers, limit switches, ac relay, transformer, and start capasitor, and installed a new digital non programmable t-stat. I wireed everything according to the wiring diagram for the furnace. I have a few small problems. 1st. On the t-stat, the Auto/On switch for the fan when turned to On the blower comes on as it should but the Suto/On switch in the furnace when switched to On the blower does not come on. Now when I switch the 2 wires on the ac relay that go to the motor 1 wire for each speed the switch in the furnace will work but the tstat switch will not?
    2nd problem, when the heat comes on and the tstat is satisfied the blower will cut off as it should but the heating elements will come back on one more time but blower will not come on, it will heat up till the limit switch cuts it off after the limit cuts it off it will stay off till the tstat turns the heat back on.? I have checked and tested all parts and they test fine except I and getting odd reading at the really I tried 2 other new replacement relyas and get the same reading. I get voltage when I am not supposed to and no voltage when I am supposed to across terminal 2&4 and 6@5 on the relay??
    Thanks
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Jan 24, 2008, 10:08 PM
    If you have no heat pump just disregard the heat pump wiring.

    http://www.nordyne.com/Literature/707555.pdf

    Typical Inertherm electric furnace wiring diag.

    http://www.nordyne.com/Literature/707716c.pdf

    Service manual later model

    http://www.nordyne.com/Literature/359a.pdf

    I have no solution for your problem since I am not there to see it or test it.

    Above are typical wiring diagrams for your brand of furnace. They are not for the exact model but all models are about the same. Both high and low voltage are included.
    Good luck.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search


Check out some similar questions!

My intertherm furnace pilot lights but furnace won't kick on [ 5 Answers ]

I need some diagnostic help. We have a full propane tank. A new burner plate (last year) and the blower works. We light the pilot but the knob should pop up after one minute thus lighting the furnace. It won't pop up. What part should we replace? The furnace is a 17 year old Intertherm MGH...

Intertherm electric furnace--is there a reset button anywhere? [ 4 Answers ]

My furnace quit working after a power outtage and I have tried and re-tried tripping and re-setting all the breakers a couple of times. I have shut all the buttons on the furnace off and back on as well. My question is this: Is there a reset button on it somewhere? :confused: I have been...

Intertherm Furnace [ 4 Answers ]

My furnace Intertherm Model # MHHB-077ABHR-06 just starteed kicking the blower in and out. The blower will run for 30 seconds, then stop, about 10 seconds later, it'll kick in again. Sometimes this will go on for 15 minutes. The flame is kicking in and it has electronic ignition.

Intertherm Furnace [ 1 Answers ]

My pilot light comes on and ignites heat exchanger but when the cover closes the flames shut down. The blower works but heat exchanger will not stay lit. I have replaced the gas valve and the thermo couple. Suggested that damper valve needed to be adjusted - where is the damper valve

Intertherm 53,000btu electric furnace [ 1 Answers ]

The heating element turns on, and off in a few seconds, but the blower doesn't take off. Any suggestions would be appreciated.


View more questions Search