    Intermittent Code 31 on Bryant Plus 90
    I have a Bryant 350MAV036080 furnace which sometimes gives me a 31 code on the LED. It will run fine for a few cycles then I'll hear the thermostat click for heat and the furnace won't run. I'll check the code and lo and behold, it's 31. If I leave it alone for about 15 min, it'll kick back on and run fine for a few more cycles.

    I've tried everything: cleaned the condensate trap and the hoses which lead to it, replaced the pressure switch, tested the condensate pump, replaced part of the vent PVC and I still can't get the unit to work 100% of the time. The vent PVC APPEARS to be clear outside. I live in a condo where it's hard to get to the actual pipe. I'm beginning to think it's the control board, does this sound like a symptom of a faulty board? Am I missing something else I should try? Thanks.
    taftsj's Avatar
    taftsj Posts: 4, Reputation: 1
    New Member
     
    #2

    Jan 4, 2009, 08:06 AM
    I had a 31 code on my Bryant plus 90 - repair guy found air switch not closing- ventor would not run. He put in conversion kit #325878-751 - now works fine!

    John in Stratford ON
    matt63634's Avatar
    matt63634 Posts: 4, Reputation: 1
    New Member
     
    #3

    Jan 4, 2009, 08:34 AM
    Quote Originally Posted by taftsj View Post
    I had a 31 code on my Bryant plus 90 - repair guy found air switch not closing- ventor would not run. He put in conversion kit #325878-751 - now works fine!

    John in Stratford ON
    Thanks. Was your furnace intermittent with code 31 or was it always not working?
    taftsj's Avatar
    taftsj Posts: 4, Reputation: 1
    New Member
     
    #4

    Jan 4, 2009, 08:45 AM
    It was intermittent at first and then it quit altogether.
    matt63634's Avatar
    matt63634 Posts: 4, Reputation: 1
    New Member
     
    #5

    Jan 4, 2009, 12:54 PM

    Okay, some success (I think). I took the cover off to the blower compartment where the circuit board is, and taped the kill switch down so it would run w/o the cover. After the thermostat clicked on for heat and nothing happened, I wiggled the wiring harness which connects the pressure switch to the circuit board - started right up. I think this is my problem. Now, is it the harness or the circuit board which is bad?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #6

    Jan 4, 2009, 01:14 PM
    Remove and replace the wire and connector a few times it might be corrosion
    taftsj's Avatar
    taftsj Posts: 4, Reputation: 1
    New Member
     
    #7

    Jan 4, 2009, 01:17 PM
    I don't know. My work order says "changed out integrated Bd." So I guess it was the board.

    John
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #8

    Jan 4, 2009, 01:27 PM
    I'll bet it is the pressure switch. Try this: next time the LED is displaying 31, nudge the wires where they connect to the p/s. If LED becomes steady, the switch is bad.
    matt63634's Avatar
    matt63634 Posts: 4, Reputation: 1
    New Member
     
    #9

    Jan 4, 2009, 01:28 PM

    Thanks. I've already replaced the pressure switch, and messed with the wires. I think it's fine.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Carrier Code #34 - intermittent [ 4 Answers ]

Hi: I have a Carrier 800 VS 58CVX070. Installed in 2003 A few weeks back we had a power outage and since then the Furnace has been a little funky. The main problem is that the trouble is intermittent. I keep getting status #34. Usually it happens late at night so, everything seems fine all...

Bryant plus 80 code 33 and cycles [ 8 Answers ]

Hi, I've got a ten year old bryant plus 80 furnace that, reads a code 33 while it cools, it is a solid while fired up but it constantly cycles. I've checed the condenser it looks clean on both top and bottom , filter is clean, all returns are open. Would making anouther return somewhere in the...

Bryant Plus 80 Code 33 [ 10 Answers ]

I have a Bryant Plus 80 that is throwing a error of 33 (limit or flame roll out switch is open). The last time this happened was because the hot surface igniter was broken (frequent problem as my furnace has a tendency to short-cycle). I had picked up a couple extra ones so I had them on hand to...

Bryant Thermostat Has Intermittent Blank Display [ 4 Answers ]

I have a Bryant Furnace with the Bryant thermostat that came with the unit. This is a non-programmable thermostat and is powered by electric (no battery power). The problem is intermittent but while the furnace is running sometimes there is no display on the thermostat. Pressing the up/down...

1993 Honda Accord Intermittent Code 15 [ 1 Answers ]

My son has a 1993 Honda accord with an intermittent code 15. When the check engine light comes on the car will not start or run. If you let the car sit for awhile, the check engine light goes out and the car will start and run again. Could someone please tell me how to diagnose the problem...


View more questions Search