    Installing Honeywell Thermostat
    I'm installing new thermostat - all wires/lettering corresponds from old to new with the exception of new one has a slot for "w"but I have two wires left "w1" and "w2". "W1" is tan and "w2" is yellow. Thanks for the help!
    Joshdta's Avatar
    Joshdta Posts: 2,549, Reputation: 45
    Ultra Member
     
    #2

    Apr 25, 2009, 04:01 PM

    Do you have a heat pump? Or gas heat?
    sgia's Avatar
    sgia Posts: 8, Reputation: 1
    New Member
     
    #3

    Apr 25, 2009, 04:04 PM
    Neither - both ac and heat are electric - house built in 70's
    Joshdta's Avatar
    Joshdta Posts: 2,549, Reputation: 45
    Ultra Member
     
    #4

    Apr 25, 2009, 04:08 PM

    OK do you still have the package your new stat came in? If so tell me what it says, like does it say 2 heat 2 cool or single stage heat plus cool.
    Joshdta's Avatar
    Joshdta Posts: 2,549, Reputation: 45
    Ultra Member
     
    #5

    Apr 25, 2009, 04:09 PM
    You may need to get a 2 heat t-stat, or put both wires on w
    sgia's Avatar
    sgia Posts: 8, Reputation: 1
    New Member
     
    #6

    Apr 25, 2009, 04:13 PM
    It's model rth600d - which is not on honeywell wesite for some reason - it says compatible with heating and cooling systems - not compatible with electric baseboard heat or heat pumps - doesn't exactly state what you are asking. New one has slots for 4 wires - I have 5 wires.
    Joshdta's Avatar
    Joshdta Posts: 2,549, Reputation: 45
    Ultra Member
     
    #7

    Apr 25, 2009, 04:15 PM

    OK tell me what colors you have, and where you have put them..
    sgia's Avatar
    sgia Posts: 8, Reputation: 1
    New Member
     
    #8

    Apr 25, 2009, 04:22 PM
    Green - g: red - r: blue - y
    Joshdta's Avatar
    Joshdta Posts: 2,549, Reputation: 45
    Ultra Member
     
    #9

    Apr 25, 2009, 04:26 PM

    Does your outdoor unit run during heating and cooling or just cooling?
    sgia's Avatar
    sgia Posts: 8, Reputation: 1
    New Member
     
    #10

    Apr 25, 2009, 04:28 PM
    Just cooling
    Joshdta's Avatar
    Joshdta Posts: 2,549, Reputation: 45
    Ultra Member
     
    #11

    Apr 25, 2009, 04:31 PM

    OK if it runs in just cooling then you have 2 options. You can take the t-stat back and get one for 2 heat. Or you can keep that one and put both wires under the w terminal. Your old t-stat was wired so that your heat would come on in stages
    sgia's Avatar
    sgia Posts: 8, Reputation: 1
    New Member
     
    #12

    Apr 25, 2009, 04:31 PM
    Fyi - it's a rth 6400d not 600 - I typed it wrong - sorry!
    sgia's Avatar
    sgia Posts: 8, Reputation: 1
    New Member
     
    #13

    Apr 25, 2009, 04:32 PM
    Thank you so much! I'll let you know if this soccer mom did it!
    sgia's Avatar
    sgia Posts: 8, Reputation: 1
    New Member
     
    #14

    Apr 25, 2009, 04:58 PM
    So far so good - nothing exploded nor caught fire - ha!ha! Thanks again!

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Trouble installing honeywell thermostat [ 6 Answers ]

I have a very old thermosat that has six wires hooked up to it now. It is labeled 2-white wire 0-brown wire B-blue wire R-red wire Y-yellow wire G-green wire The honey well thermostat I bought has 5 connections Rh, Rc, W, Y, G with it only having 5 and my current has 6 is this thermostat...

Installing new honeywell thermostat old wiring odd [ 3 Answers ]

Hi I bought a new thermostat a Honeywell rth7400 for heatpump & aux (oil as back up) The old thermostat was a totaline with a separate toggle installed underneath it to switch back and forth from auxiliary to heat pump I have 8 wires coming out of the wall I have tagged them as followed:...

Installing a Honeywell programmable thermostat [ 1 Answers ]

I am replacing an old mercury thermostat with a honeywell rth7000. I have a heat pump Unit. Current Mercury wired as such: Red wire to R Brown wire to T Orange wire to O Green wire to G Yellow wire to Y Blue wire to B

Installing RTH7400 Honeywell Thermostat [ 1 Answers ]

I am replacing my (old) Honeywell T8411R thermostat with a (new)Honeywell RTH7400 programmable thermostat. I need help wiring to the new thermostat. My H/C system is a heat pump system. The old thermostat is wired to the following terminals: W1 - White W2 - Brown G - Green R - Red C - Blue...

Installing Honeywell RTH230B thermostat [ 1 Answers ]

I'm having trouble installing a Honeywell RTH230B thermostat. When I took off the old one, I properly labeled the colored wires and turned the electricity back on, but the furnace won't kick on. I checked to see what color wires are coming out of the furnace, and it's just two of them-- green and...


View more questions Search