    kmphx72's Avatar
    kmphx72 Posts: 10, Reputation: 2
    New Member
     
    #1

    Sep 1, 2007, 03:14 PM
    Hunter thermostat reads no a/c power
    We just purchased a hunter thermostat model 44760 to replace the old thermostat when our a/c went out and it reads no a/c power. We have a trane heat pump. We've also replaced the fuses outside next to our heat pump and nothing is working. I believe our wiring is correct. Can anyone help? Thanks. Also, on our old thermostat the brown wire didn't go to anything. The other colors we have are red, blue, green, orange, white, black, yellow.
    esquire1's Avatar
    esquire1 Posts: 2,483, Reputation: 209
    Ultra Member
     
    #2

    Sep 1, 2007, 03:47 PM
    Check the transformer. Do you have 24 volts on the secondary side? Check out the "stickey" at the top of this forum for thermostats. You can also jumper R, G&Y at stat. Does the ac run with these jumpered?
    kmphx72's Avatar
    kmphx72 Posts: 10, Reputation: 2
    New Member
     
    #3

    Sep 1, 2007, 04:23 PM
    I believe it has the 24 volts. I'm not very knowledgeable about jumpers and such. Where would I find the transformer? Thanks.
    hvacservicetech_07's Avatar
    hvacservicetech_07 Posts: 1,083, Reputation: 75
    Ultra Member
     
    #4

    Sep 1, 2007, 04:36 PM
    It sounds like you may either be miswired or you have a loose common. List the old and new wiring connections, maybe we can help...
    biggsie's Avatar
    biggsie Posts: 1,267, Reputation: 125
    Ultra Member
     
    #5

    Sep 1, 2007, 05:43 PM
    In your furnace there is 24 volt transformer and powers the brains of your unit...

    There will be two wires from furnace to the thermostat ***(find out what color

    Of wires come off the red wires on transformer)***they go to R and C in

    Thermostat

    Now you need to put green on terminal G in the thermostat to run the fan...

    This should be a good place to test your work -- put thermostat together

    Turn power on to furnace and turn fan to continuous -- fan should run

    If you get this far get back to me to go from there -- Does fan run??
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #6

    Sep 1, 2007, 07:35 PM
    Many of the new stats require a connection to common so that the thermostat can be powered. You need to have a wire on (C) and (R) of the thermostat. You should have 24 VAC at all times at these terminals. This is what that error means - 24 VAC is missing

    You need to compare the terminals at the furnace and the terminals at the stat with wires used. Sometimes, although rarely, some stupid installer will switch wire colors in the middle of the run.

    On newer furnaces there may be an automotive type fuse for the 24 VAC. That should be checked too.
    kmphx72's Avatar
    kmphx72 Posts: 10, Reputation: 2
    New Member
     
    #7

    Sep 11, 2007, 06:32 AM
    Thanks everyone for the help. I'm sorry for not getting back sooner. We did look at the wiring again and found the blue as the common. And we also made sure that none of the other connections were loose. However, we don't have anything to make sure that we have the 24 volts. We decided to call a technician to come look at our heat pump and let us know what else is wrong. I'll be getting back if I need more advice from everyone. Thanks again.
    kmphx72's Avatar
    kmphx72 Posts: 10, Reputation: 2
    New Member
     
    #8

    Sep 12, 2007, 01:00 PM
    Thanks again. The technician told us that the problem was the transformer, so we got that replaced. Now it's working again. Thanks for all the info. I learned a lot.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Hunter thermostat wiring? [ 1 Answers ]

I have a 25 y/o unit, one part of furnace in the attic and a outside unit all electric The outside says magic chef The old thermostat is a honeywell with the following wiring: Wire color ----------position Green G Red RC also jumpers to RH...

Hunter thermostat 44110 [ 2 Answers ]

I have hot water baseboard heat, and installed the hunter digital thermostat 44110, and followed the directions as directed, I had had wires W, Y and RH, I marked and installed Each of the wires, and put them where they were marked on the thermostat. I felt well and all of the lights ( temp,...

Need Help with Hunter Thermostat Please [ 4 Answers ]

I have a Payne PF1MNC hvac, and just replaced my White Rodgers thermostat (It wasn't blowing hot air or kicking in in Auto mode) with a Hunter 44155C. There were 4 wires attached: G to G R to Rh (with jumper) Y to Y1 W to W And an unattached B I attached them the same to the Hunter:

Need Help - Getting "No AC Power" with Hunter Thermostat [ 2 Answers ]

Installed a new Hunter Thermostat today and I am getting "No AC Power". So I looked in the fuse box and the 5V that connects the Black and Red wire was blown. I since replaced the fuse with a new one and it also blew. Please help. It gets pretty cold at night.


View more questions Search