    How to manually open honeywell V8043F1036
    I'm troubleshooting my heating system and I think a zone valve is stuck closed. Thermostat is calling for heat but the hot water pipes (hot water baseboard heat) are not heating up. I have four zones and the others are heating just fine. I replaced the thermostat so have narrowed it down to zone valves.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Feb 14, 2013, 03:35 PM
    Most zone valves will allow you to open them manually so open it up and see if it gets hot. Move the lever to open.

    Manual Lever
    The V8043 normally closed valves can be opened manually by moving the manual lever slowly and firmly to the MAN. OPEN position and pushing up to the stop. The stop permits the valve to be locked in the open position. The valve returns to automatic position when it is energized.

    Read it here

    http://www.alpinehomeair.com/related...ntructions.PDF

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

How to manually engage a honeywell zone valve v8043e1004 [ 2 Answers ]

My zone valve, a V8043E1004 will not engage to open. When I turn on the thermostat the manual control arm is very sloppy and easy to move back and forth. So I move it all the way to the left (looking at it from the top) to the manual side, I turn off the thermostat and come back out and the arm has...

Honeywell zone valve seems stuck open [ 19 Answers ]

I manually opened one of my home's five Honeywell zone valves (V8043E-1012) by mistake. I meant to open a different valve. The one I opened had its thermostat set to its lowest temp setting, as it controls heat to a space I hardly ever heat. The next day the valve was still in the open position...

Do I manually light the pilot [ 0 Answers ]

My furnace was running fine as of this morning. I noticed it felt cold. Checked temp and it is 58, set the furnace to come on via thermostate, Nothing happened, Checked the furnace and no pilot. Power to unit working. How do I get it running? 7p on Sunday; have to do it myself. Thanks

Honeywell heating zone valves does not open [ 3 Answers ]

I installed a honeywell zone valve.It won't open in the manual position.I did not wire it yet.What's wrong with the valve?

How to manually open garage [ 2 Answers ]

My garage door opener is stuck it will not open all the way. It acts like it is locked when I try to pull up manually. It slams close when I release the manual pull to close. How can I get my cars out-i got to go to work!! Help??


View more questions Search