    How do I check the sequencer in my intertherm furnace?
    My Interthrem electric furnace will not run in automatic;I've changed the sequencer per suggestions,but to no avail what can I do?
    WillyBill's Avatar
    WillyBill Posts: 5, Reputation: 1
    New Member
     
    #2

    Mar 17, 2010, 12:43 PM
    How do I check the sequencer in my intertherm furnace?
    I have an Intertherm furnace that will not run in automatic. I've changed the sequencer per instructions and also the t,stat. And it still will not run... help please. I am a hands on type of guy.
    wmproop's Avatar
    wmproop Posts: 3,749, Reputation: 91
    Ultra Member
     
    #3

    Mar 17, 2010, 03:21 PM
    You will need a meter,, check power going in and across from the same post check for power coming out,, be careful 230 V bits pretty hard
    WillyBill's Avatar
    WillyBill Posts: 5, Reputation: 1
    New Member
     
    #4

    Mar 18, 2010, 09:09 AM
    My furnace will not work after changing sequencer and t.stat,per suggestions,any help
    I have a Intertherm model#FEH-012HA heat only furnace,I disabled the t.stat to check the sequencer(the fan and the strips stayed on)I did this by suggestion. I also changed the t.stat and still the fan will not run in auto.(I left this part out)what do I do now? I'm no electrician but I am a hands on guy and enjoy learning new things, Thank You for any help.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #5

    Mar 18, 2010, 10:12 AM
    Quote Originally Posted by WillyBill View Post
    I have a Intertherm model#FEH-012HA heat only furnace,I disabled the t.stat to check the sequencer(the fan and the strips stayed on)I did this by suggestion. I also changed the t.stat and still the fan will not run in auto.(I left this part out)what do I do now? I'm no electrician but I am a hands on guy and enjoy learning new things, Thank You for any help.
    The thermostat has nothing to do with the FAN in AUTO mode since this function is controlled by the heat sequencer in most units. In a heat only application only two wires are used and that is the red and white going to the R-RED and W-WHITE on the thermostat.

    As a guess on my part it seems like you might have a sequencer that is not functioning properly OR something is wired wrong.
    WillyBill's Avatar
    WillyBill Posts: 5, Reputation: 1
    New Member
     
    #6

    Mar 18, 2010, 03:15 PM

    To HVAC 1000, thanks I'll go a little slower. You were most helpful; Thanks again
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #7

    Mar 18, 2010, 09:30 PM
    No problem. Sometimes these things need to be traced down in some logical order or the problem will remain.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

What can happen if the sequencer fails on my electric furnace? [ 7 Answers ]

My electric furnace sometimes wants to keep heating without ever shutting off. Changed the thermostat but, it still happens. I can tap briskly on the sequencer and it will shut off, and it will run as it is supposed to. But, then it can happen again. Is this probably a problem with the sequencer?

How does my sequencer go bad on ny electric furnace [ 1 Answers ]

After making sure my t stat was not the problem I replaced my sequencer... the problem was that my furnace would not quit making heat... worked for a few weeks and then the same thing happened but now I think one of the thermal fuses blew... what makes the sequencer go bad?

Intertherm furnace e2eb-017hb runs briefly, shuts off, then furnace just clicks [ 3 Answers ]

I have an Intertherm furnace, e2eb-017hb. It comes on briefly, blows warm air, then shuts off, and a clicking sound comes from the coil contacts area. I have tested the t-stat, and also replaced a coil contact, thinking that was the problem. I would appreciate any help on what to do next.

My intertherm furnace pilot lights but furnace won't kick on [ 5 Answers ]

I need some diagnostic help. We have a full propane tank. A new burner plate (last year) and the blower works. We light the pilot but the knob should pop up after one minute thus lighting the furnace. It won't pop up. What part should we replace? The furnace is a 17 year old Intertherm MGH...

Intertherm Furnace sequencer [ 1 Answers ]

How do you replace the sequencer on an Intertherm Furnace by Central Electric? The model # is FEH-012HA-03 Appliance # E0000088245, 240v 60hz 1ph, 51.3 amps.


View more questions Search