    Honeywell RTH110B Thermostat
    My furnace thermostat was taken off the wall while moving furniture now I have 3 wires hanging out of a whole in the wall. I would like to hook those wires up to Honeywell RTH110B but I’m not sure which wire goes where. On the red wire I have 24vac, on my white wire I have 12vac and I have a blue wire that has nothing on it. Any help I can get with this would be fantastic. :rolleyes:
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #2

    Oct 20, 2006, 05:02 PM
    24 volts to what? 12 on the white wire?

    Usually there is a 24 volt AC transformer in the furnace with the secondary winding connected to a red wire running to the thermostat and a blue wire, common, to the gas valve, A/C relay, and fan relay. From the thermostat there will be white wire to the gas valve, yellow to the A/C, and green to the fan. The thermostat is wired to switch the power from the red to the white, yellow, and green as needed with the blue completing the circuit. Most thermostats and furnaces have the contacts labeled R, B or C, W, Y, and G for the corresponding wire colors. It may be wired to have the A/C control wires return to the furnace and its controls and then a second wire goes to the A/C unit. Internal wiring may replace the green wire if the thermostat does not give you the option of fan only or continuous fan. Digital or programmable thermostats may need the blue wire connected to them.
    omzig's Avatar
    omzig Posts: 119, Reputation: 19
    Junior Member
     
    #3

    Oct 21, 2006, 10:04 PM
    Maybe the manual would help. If you don't have one, here is a link to it: RTH110B

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Honeywell Thermostat Went Insane [ 8 Answers ]

I have a Honeywell Chromotherm III programmable thermostat (probably 10 years old) that controls my heat pump. Since the temperatures in Phoenix have become moderate, the thermostat was in the off position. Yesterday I left the house in the morning and returned about 6 PM. The temperature in the...

Honeywell thermostat [ 11 Answers ]

I installed a Honeywell CT87A 4447 thermostat this summer. It worked fine with my air conditioning, but I am having a problem with it controlling my furnace. It will turn the furnace on and I can turn the fan on manually, but when set to auto the fan does not come on. The thermostat has the...

Please Help w/Replacing Honeywell Thermostat... [ 3 Answers ]

Hi! I've just removed my Honeywell Thermostat and am trying to replace it with a Noma programmable tstat... but am having problems with the wiring. There are 5 wires coming out of the wall - Green, Black, Orange, Red and White, and only 4 posts on the Noma tstat (Green, Red, Yellow and White). ...

Honeywell rth230b thermostat [ 3 Answers ]

We hooked up the honeywell programmable thermostat and it was working fine for 10 days or so until this weekend when the temperature should be at 67 all day from 6am to 10pm and 62 from 10pm until 6am on sat and sun. this weekend the thermostat does not bring the temp up to 67 but it leaves it at...

Honeywell RTH230B Thermostat [ 1 Answers ]

I recently installed Honeywell #RTH230B thermostat to replace and old Honeywell # T87F( old round non digitital type). I have oil burner with basebaord water heat. Since my olf thermostat was 2 wire only and I have no AC I pulled the jumper wire between Rh and Rc as per the instructions. Thj9is...


View more questions Search