    honeywell g600ax-1 no gas thro to system
    I'm not getting any gas to the line.. there is gas going into it but when I turn it on no gas goes to the ignition every once in a blue moon it will light then shut off like 1 -2 min latter I have no clue what to do I think it is the values that sitt right under I think there are not lifting or what ever they do to let the gas thro
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #2

    Feb 20, 2009, 04:20 PM
    If you have a voltmeter, check for 24v at the gas control when the unit is attempting to operate. If present, but ignition is unsuccessful, you may have a faulty gas control or inadequate gas supply pressure.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Honeywell system A/C not working? [ 7 Answers ]

Holy Crap it is 82 degrees in the house. I have tried many different settings, read the dang manual can't find out how to get the a/c to come on. Should it be on Auto or should I have it on fan? What temp to set it to? I just tried to look through the frequently asked questions but it didn't...

Wiring changes: Johnson Controls G600AX-1 With Honeywell S8610U Gas Ignition Control [ 7 Answers ]

This is my very first post so... Hello everyone. and here is my question: I am replacing a Johnson Controls Pilot Gas Ignition control unit with a Honeywell 8610U and I am a little confused on how to connect all the wires. The wiring on the Johnson Controls unit is as follows: Main Valve...

Honeywell zone control system [ 1 Answers ]

I'm installing a Honewell zone control system (Honeywell HZ311K 1 Heat / 1 Cool TrueZONE Zoning Kit). The kit comes with a low volt transformer, but my existing furnace has an onboard transformer wired into it. Do I need to install the second transformer just to be able to run the control panel...

New Thermostat, Honeywell, on old system, Trane [ 1 Answers ]

We just installed a Honeywell Thermostat on our Trane heating system/heat pump circa 1988. The system comes on for about 20 seconds, turns off, comes on again for about 20 seconds and turns off, then it will come on shortly thereafter and stay on for awhile. We had a professional hook up the...

Carrier or Honeywell Zone System? [ 2 Answers ]

Hey all! I have a 2700sqft home that is two stories half of that is upstairs and half down. I have a 4 year old 5 ton all in one AC/Heat unit and only one return in the house which is downstairs. I have been getting estimates on getting a second return put in upstairs along with a zone system...


View more questions Search