    Honeywell Blank Thermostat
    I have a Honeywell T8011R thermostat. It is blank. I have 120 vac coming in, the transformer has 28 vac coming out. The 5 amp fuse is fine and the control switch is on. On the circuit board with the 5 amp fuse, the brown wire from the transformer shows 28 vac, the double brown wire under it is 0 vac. The red wire under that shows 28 vac. The grey wire under that one shows 0 vac. And the last red wire under that one reads 28 vac. I think the circuit board may be the problem but I am not sure. Is that easy to replace or should I check something else first?
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #2

    Sep 4, 2007, 04:01 AM
    Need a little more info... what type of furnace/air handler do you have (brand/model)? Check for 24 volts where thermostat wires connect to indoor unit (R-C). You may need to hold or tape the blower door interlock switch (if present).
    mustang4's Avatar
    mustang4 Posts: 2, Reputation: 1
    New Member
     
    #3

    Sep 5, 2007, 07:24 PM
    The problem turned out to be a float switch. The air handler is upstairs and has 2 drain lines. The lower one runs outside. The other is capped with a float switch. I was able to measure the volatge of the red wire at the base of the thermostat and it was reading under 3 vac. I next read the red wire in the bundle of thermostat wiring and it had 14 vac. I traced the white wire that was attached to the red wire to the float switch in the pvc drain. When I pulled it out I found it was filled with water. I removed the water in that line and cleared the rust that had built up in the air handler so that it would drain through the primary pvc drain line. It works fine now.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Programmable thermostat went blank [ 12 Answers ]

Our thermostat (which has been serving solely as a thermometer since the last time we used the heat in the spring) blanked out yesterday afternoon. I checked the inside temp. during the day, then last evening the face was completely blank. It is completely unresponsive to any button pushing. I...

Honeywell T8001 thermostat goes blank [ 2 Answers ]

I have a 5 hear old dual zone Heat/AC system with two Honeywell T8001 thermostats. These units don't use a battery. About once a year one of the T8001s goes blank. Since the T8001 clips to a bracket on the wall, I mobilized my advanced troubleshooting skills and simply swapped the units. The...

Honeywell T8001 Thermostat - Blank Display [ 1 Answers ]

Kids while playing in the backyard were banging against the outside compressor unit and I found later that the display on the thermostat is now blank. So I can not switch on heating or air conditioning. Since my house has two units one for upstairs and one for downstairs, I tested by swapping the...

Blank Thermostat [ 6 Answers ]

Hi Guys, I had the A/C unit running fine today... then all of a sudden my thermostat went blank... It was raining on and off today here in Plano, Texas... It is a Carrier A/C furnace unit, controlled by a Honeywell Thermostat... This thermostat gets its power from the unit itself... In the...

Honeywell digital thermostat dead/blank [ 2 Answers ]

No flashing or blinking lights or numbers. No read out at all on thermostat. No batteries, it bleeds power off the furnace I believe. York natural gas furnace. I checked the breakers, they are all on. The pilot light is on. This has happened before, about 2 weeks ago. I had a service guy...


View more questions Search