    cindymega1's Avatar
    cindymega1 Posts: 1, Reputation: 1
    New Member
     
    #1

    Nov 5, 2006, 11:41 AM
    My Heater Will Heat then Cool?
    The central heating and air unit we have is approximately 2 years old. In the summertime, the AC operates properly. However, in the winter months, the heating unit seems to be malfunctioning. We will set the thermostat to a certain temperature and the heater will heat the house to the set temperature but then the AuX Heat comes on and cools the house down once the house is cooled down the Aux Heat goes off and the heater will heat the house back to the set temperature and the cycle continues until we turn the thermostat off. Then when we turn the thermostat back on it will work properly for awhile and then the cycle of heating and cooling will begin again.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #2

    Nov 5, 2006, 12:04 PM
    If the thrmostat is hooked up right, the control board is bad. There is a sticky that gives sources for thermostat directions. I think there is another somewhere that requests complete information in questions. Dig up the directions and make sure the thermostat is hooked up right. If so, post back with more information.
    Morganite's Avatar
    Morganite Posts: 863, Reputation: 86
    Senior Member
     
    #3

    Nov 5, 2006, 12:15 PM
    Quote Originally Posted by cindymega1
    The central heating and air unit we have is approximately 2 years old. In the summertime, the AC operates properly. However, in the winter months, the heating unit seems to be malfunctioning. We will set the thermostat to a certain temperature and the heater will heat the house to the set temperature but then the AuX Heat comes on and cools the house down once the house is cooled down the Aux Heat goes off and the heater will heat the house back to the set temperature and the cycle continues until we turn the thermostat off. Then when we turn the thermostat back on it will work properly for awhile and then the cycle of heating and cooling will begin again.
    Your heater/AC control should have three settings: Heat; AC; OFF.

    When the weather is cold, set it to "HEAT". If the AC cuts in at any time during this cycle, the control box is up the spout (defunct) and needs to be replaced.

    M:)
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #4

    Nov 5, 2006, 01:39 PM
    Sounds like you have a heat pump. What is the actual temperature that comes out of the vent when you think it is cooling?
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #5

    Nov 5, 2006, 07:54 PM
    Sounds like the thermostat is not wired right. It takes at least 5 wires@ the stat to make a heatpump work. Make sure the W2 wire is connected from the stat to the fan coil.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Heater will heat, but fan will not turn off [ 3 Answers ]

Hi. I have a big problem that is killing me. I have a central Heat and AC unit that works well, but the fan won't seem to turn off. The AC and Heat works well, but the fan just keeps on running. I was gone for 3 months for ARMY business and my wife did not know that this was not working right,...

Gas forced air heater won't turn heat on [ 6 Answers ]

My honeywell thermostat electric, shows "filter" change light blinking and won't turn on the heater when turned up. The thermostat will 'click' when temp turned up and I can manually turn on the fan but no fire in the heater. The thermostat is 1 year old, filter changed

NO HEAT! Janitrol heat pump and AC system. Changing to Lux Thermostat. Wiring issue. [ 11 Answers ]

I have a Janitrol A/C and heat pump system. I replaced the thermostat with a Lux T9000LC The A/C works fine, but the heater does not. I have it wired as follows: G - Green Y - Yellow W - White RH - Pink B -

Honeywell thermostat heat/cool in Rheem 2 stage furnace? [ 1 Answers ]

I have a Honeywell 1 Heat/1Cool thermostat (TH6110D1013) that I would like to use with a Rheem 2 stage gas heat furnace. I think it is possible but would I get the same benefits as having a thermostat with 2 heat/1 cool? Would I just connect the W terminal on the Thermostat to the W2 on the...

HELP, it's not cool in here [ 1 Answers ]

Woke this morning to a half way cool home. Heard the central air conditioner shut off and all of a sudden I hear this clanging noise from the furnace. HELP:eek:


View more questions Search