Goodman gmp075-3 flashing code 4
Indicates a open limit switch
Here some info
I'm installing a used funace,, I've had it checked out by a certified guy
And we had it running while we checked it out... worked great...
Then I installed it in my house,, when I hooked it up and turned it on
The inducer comes on, and the main blower comes on
And then the led flashes 4 times,, then waits 5 secs then flashs 4 times
Continuously... ive check the wire connections, same result...
Now I'm thinking there is 4 limit switches.. right??
How do I narrow it down to which one? continuity test??
Any other ideas??
Thanks much
Like to have some heat...
Heat I good
Thanks
Bryen
|
|
|
Ultra Member
|
|
Feb 8, 2009, 10:11 AM
|
|
Check the ones strung together with purple wires first-press the small tab in the center, if any "click" they were tripped. Don't forget the one under the blower shelf, or the one on the front of the blower (if present-look behind circuit board mounting plate). Check the main limit too (red wires, behind the gas control). If you have a voltmeter, check for voltage across each switch with the unit powered. If you measure approx. 24v, the switch is open.
|
|
|
New Member
|
|
Feb 8, 2009, 06:18 PM
|
|
Originally Posted by KC13
Check the ones strung together with purple wires first-press the small tab in the center, if any "click" they were tripped. Don't forget the one under the blower shelf, or the one on the front of the blower (if present-look behind circuit board mounting plate). Check the main limit too (red wires, behind the gas control). If you have a voltmeter, check for voltage across each switch with the unit powered. If you measure approx. 24v, the switch is open.
Sweet man,, I got it running,, was just the switch under the main blower wire, was disconnected
OK,, my next question,,
Seems that when the temp has been met and is shutting down,, the main blower
Seems like it runs way to long,, and blows a lot of excess cold air
Other than that, I have wonderous heat..
Thanks for the quick response
Bryen
|
|
|
Plumbing Expert
|
|
Feb 8, 2009, 06:32 PM
|
|
Is your furnace a two stage furnace? If so, there are three dip switch settings on control board. Top is for blower off time, middle is for one or two stage, bottom is for auto or five minute (first and second stage) switchover. Please let me know what you have. I can't remember what the top setting is on from factory, so if you could let me know what it says, I could try to help you out.
|
|
|
New Member
|
|
Oct 16, 2009, 10:36 AM
|
|
Where is the main limit switch
|
|
Question Tools |
Search this Question |
|
|
Add your answer here.
Check out some similar questions!
Goodman GMP075
[ 1 Answers ]
the furnace is tripping on high limit , not rollout. It will initiate a call for heat. The flue fan will run the air switch will make and the ignitor will glow. The MV comes on and the furnace lights. It continues to run for appr. 2 minutes and the high limit will open. It is not a variable high...
Goodman gas furnace gmp075 3
[ 2 Answers ]
Hi , my goodman furnace gmp075 3 furnace ,inducer turns on ignitor glows ,burners fire for about 5-7 sec,then turn off blower doesn't come on,but if I let it cycle about 5 times then the blower does come on and it works fine,can anyone tell me what's wrong, thank you
Goodman gmp075-4 problems
[ 2 Answers ]
Problems with My goodman gmp075-4 furnace. The blower motor runs regardless of thermostat controls. The induction motor doesn't come on, unless
The limit switch is unhooked... then she spins like a champ. I removed the induction assembly and cleaned it all out, including the flue. The trouble...
View more questions
Search
|